It is possible to block the
SPR_CHR_ALM
alarm signal by activating the
BLOCK
binary
input.
7.1.4.8
Gas pressure supervision
The gas pressure supervision subfunction monitors the gas pressure inside the arc
chamber.
The operation of the subfunction can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
A071113 V2 EN
Figure 464:
Functional module diagram for circuit breaker gas pressure alarm
The gas pressure is monitored through the binary input signals
PRES_LO_IN
and
PRES_ALM_IN
.
Timer 1
When the
PRES_ALM_IN
binary input is activated, the
PRES_ALM
alarm is activated
after a time delay set with the
Pressure alarm time
setting. The
PRES_ALM
alarm can be
blocked by activating the
BLOCK
input.
Timer 2
If the pressure drops further to a very low level, the
PRES_LO_IN
binary input becomes
high, activating the lockout alarm
PRES_LO
after a time delay set with the
Pres lockout
time
setting. The
PRES_LO
alarm can be blocked by activating the
BLOCK
input.
7.1.5
Application
52CM includes different metering and monitoring subfunctions.
Circuit breaker status
Circuit breaker status monitors the position of the circuit breaker, that is, whether the
breaker is in an open, closed or intermediate position.
1MAC059074-MB A
Section 7
Condition monitoring functions
615 series ANSI
889
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......