7.1.7
Settings
Table 785:
52CM Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Acc stop current
5.00...500.00
A
0.01
10.00
RMS current setting below which engy acm
stops
Open alarm time
0...200
ms
1
40
Alarm level setting for open travel time in ms
Close alarm time
0...200
ms
1
40
Alarm level Setting for close travel time in ms
Spring charge time
0...60000
ms
10
15000
Setting of alarm for spring charging time of CB
in ms
Alarm Op number
0...99999
1
200
Alarm limit for number of operations
Lockout Op number
0...99999
1
300
Lock out limit for number of operations
Current exponent
0.00...2.00
0.01
2.00
Current exponent setting for energy calculation
Difference Cor time
-10...10
ms
1
5
Corr. factor for time dif in aux. and main
contacts open time
Alm Acc currents Pwr
0.00...20000.00
0.01
2500.00
Setting of alarm level for accumulated currents
power
LO Acc currents Pwr
0.00...20000.00
0.01
2500.00
Lockout limit setting for accumulated currents
power
Directional Coef
-3.00...-0.50
0.01
-1.50
Directional coefficient for CB life calculation
Initial CB Rmn life
0...99999
1
5000
Initial value for the CB remaining life
Rated Op current
100.00...5000.00
A
0.01
1000.00
Rated operating current of the breaker
Rated fault current
500.00...75000.00
A
0.01
5000.00
Rated fault current of the breaker
Op number rated
1...99999
1
10000
Number of operations possible at rated current
Op number fault
1...10000
1
1000
Number of operations possible at rated fault
current
Inactive Alm days
0...9999
1
2000
Alarm limit value of the inactive days counter
Travel time Clc mode
1=From Cmd to
Pos
2=From Pos to Pos
2=From Pos to Pos Travel time calculation mode selection
Table 786:
52CM Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Opening time Cor
-100...100
ms
1
10
Correction factor for open travel time in ms
Closing time Cor
-100...100
ms
1
10
Correction factor for CB close travel time in ms
Counter initial Val
0...99999
1
0
The operation numbers counter initialization
value
Ini Acc currents Pwr
0.00...20000.00
0.01
0.00
Initial value for accumulation energy (Iyt)
Life alarm level
0...99999
1
500
Alarm level for CB remaining life
Table continues on next page
Section 7
1MAC059074-MB A
Condition monitoring functions
894
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......