background image

Table 24. Electromagnetic compatibility tests, continued

Description

Type test value

Reference

Power frequency immunity
test

• Common mode

• Differential mode

Binary inputs only
 
300 V rms
 
150 V rms

IEC 60255-22-7, class A
IEC 61000-4-16

Voltage dips and short
interruptions

30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms

IEC 61000-4-11

Electromagnetic emission
tests

 

EN 55011, class A
IEC 60255-25

• Conducted, RF-emission

(mains terminal)

 

 

0.15...0.50 MHz

< 79 dB(µV) quasi peak
< 66 dB(µV) average

 

0.5...30 MHz

< 73 dB(µV) quasi peak
< 60 dB(µV) average

 

• Radiated RF-emission

 

 

30...230 MHz

< 40 dB(µV/m) quasi peak,
measured at 10 m distance

 

230...1000 MHz

< 47 dB(µV/m) quasi peak,
measured at 10 m distance

 

Transformer Protection and Control

1MRS756978 D

RET630
Product version: 1.1

Issued: 2011-05-18

26

ABB

Summary of Contents for Relion 630 Series RET630

Page 1: ...Relion 630 series Transformer Protection and Control RET630 Product Guide ...

Page 2: ...g data 62 23 Accessories 66 25 Tools 67 26 Supported ABB solutions 69 27 Terminal diagrams 70 28 References 74 29 Functions codes and symbols 74 30 Document revision history 78 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy ABB Oy assumes no responsibility for any errors that may appear in this document Copyrigh...

Page 3: ... protocols including IEC 61850 offer seamless connectivity to various station automation and SCADA systems 2 Application RET630 provides main protection for two winding power transformers and power generator transformer blocks Two pre defined configurations to match your typical transformer protection and control specifications are available The pre defined configurations can be used as such or ea...

Page 4: ...arrangement The RET630 with preconfiguration A is used for protection and control of the power transformer the REF630 with preconfiguration B protects and controls the outgoing feeder and the REF630 with preconfiguration D is used for the bus sectionalizer Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 4 ABB ...

Page 5: ...e texts shown in the HMI configuration of the LEDs and function buttons and adaptation of the default single line diagram In addition the adaptation of the preconfiguration always includes communication engineering to configure the communication according to the functionality of the IED The communication engineering is done using the communication configuration function of PCM600 If none of the of...

Page 6: ...rectional earth fault low stage LV side 1 2 Non directional earth fault low stage HV side 1 1 Non directional earth fault high stage LV side 1 2 Non directional earth fault high stage HV side 1 1 Directional earth fault low stage 2 Directional earth fault high stage 1 Stabilised restricted earth fault LV side 1 2 Stabilised restricted earth fault HV side 1 High impedance based restricted earth fau...

Page 7: ...Multipurpose analog protection 16 Control Bay control 1 1 1 Interlocking interface 4 4 10 Circuit breaker disconnector control 4 4 10 Circuit breaker 1 1 2 Disconnector 3 3 8 Local remote switch interface 1 Synchrocheck 1 Tap changer control with voltage regulator1 1 Generic process I O Single point control 8 signals 5 Double point indication 15 Single point indication 64 Generic measured value 15...

Page 8: ...t LV side 1 1 2 Three phase current HV side 1 1 Three phase voltage phase to phase 1 1 1 Three phase voltage phase to earth 1 1 1 Residual current measurement 2 2 2 Residual voltage measurement 1 Sequence current measurement 1 Sequence voltage measurement 1 Power monitoring with P Q S power factor frequency 1 1 1 Disturbance recorder function Analog channels 1 10 samples 1 1 1 Analog channels 11 2...

Page 9: ...zing resistors nor varistors are needed and as a further benefit the transforming ratio of the earthing point current transformers can differ from those of the phase current transformers Due to its unit protection character the REF protection does not need any time grading and therefore a fast protection operating time can be achieved The overexcitation protection is used to protect generators and...

Page 10: ...D FD724103 823D 4443 ACAE 412BB7906240 V2 EN Figure 2 Protection function overview of preconfiguration A Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 10 ABB ...

Page 11: ...guration Besides conventional hardwired signaling also GOOSE messaging according to IEC 61850 8 1 can be used for signal interchange between IEDs to obtain required interlockings Further the IED incorporates a synchro check function to ensure that the voltage phase angle and frequency on either side of an open circuit breaker satisfy the conditions for safe interconnection of two networks 6 Voltag...

Page 12: ...otection and condition monitoring functions of the IED The values measured are accessed locally via the front panel user interface of the IED or remotely via the communication interface of the IED The values are also accessed locally or remotely using the web browser based user interface 8 Disturbance recorder The IED is provided with a disturbance recorder featuring up to 40 analog and 64 binary ...

Page 13: ...alues By default the disturbance reports are stored in a non volatile memory The numerical disturbance report can be accessed via the local front panel user interface A more comprehensive disturbance report with waveforms is available using PCM600 11 Circuit breaker monitoring The condition monitoring functions of the IED constantly monitors the performance and the condition of the circuit breaker...

Page 14: ...he IED according to the profile of the user group 17 Inputs and outputs Depending on the hardware configuration selected the IED is equipped with six phase current inputs three inputs for the HV side and three inputs for the LV side and one or two neutral current inputs for earth fault protection Depending on the selected hardware configuration the IED includes two or three voltage inputs One of t...

Page 15: ...evices provided with mA input capabilities The enhanced scalability of the 6U variant IEDs are intended for optimized medium voltage metal clad switchgear applications where additional binary inputs and outputs are often required All binary input and output contacts are freely configurable using the signal matrix of the application configuration function in PCM600 Please refer to the Input output ...

Page 16: ... in distribution substations as defined by the IEC 61850 standard Further the IED supports the sending and receiving of analog values using GOOSE messaging Analog GOOSE messaging enables fast transfer of analog measurement values over the station bus thus facilitating for example sharing of RTD input values such as surrounding temperature values to other IED applications The IED interoperates with...

Page 17: ...at B IEC 60870 5 103 serial communication has a time stamping resolution of 10 ms Table 6 Supported communication interface and protocol alternatives Interfaces protocols1 Ethernet 100BASE TX RJ 45 Ethernet 100BASE FX LC Serial snap in Serial ST IEC 61850 DNP3 IEC 60870 5 103 Supported 1 Please refer to the Selection and ordering data chapter for more information Transformer Protection and Control...

Page 18: ...ad of auxiliary voltage supply 35 W Ripple in the DC auxiliary voltage Max 15 of the DC value at frequency of 100 Hz Maximum interruption time in the auxiliary DC voltage without resetting the IED 50 ms at Uaux Power supply input must be protected by an external miniature circuit breaker For example type S282 UC K The rated maximum load of aux voltage which is given as 35 watts Depending on the vo...

Page 19: ...V AC 110 V AC 115 V AC 120 V AC Voltage withstand Continuous 425 V AC For 10 s 450 V AC Burden at rated voltage 0 05 VA 1 Residual current 2 Phase currents or residual current Table 10 Binary inputs Description Value Operating range Maximum input voltage 300 V DC Rated voltage 24 250 V DC Current drain 1 6 1 8 mA Power consumption input 0 3 W Threshold voltage 15 221 V DC parametrizable in the ran...

Page 20: ...lead Resistance 25 Ω per lead Isolation 4 kV Inputs to all outputs and protective earth RTD resistance sensing current Maximum 0 275 mA rms Operation accuracy temperature 1 C Pt and Ni sensors for measuring range 40 C to 200 C and 40 C to 70 C ambient temperature 2 C CU sensor for measuring range 40 C to 200 C in room temperature 4 C CU sensors 40 C to 70 C ambient temperature 5 C From 40 C to 100...

Page 21: ... V AC DC Continuous contact carry 5 A Make and carry for 3 0 s 10 A Make and carry 0 5 s 15 A Breaking capacity when the control circuit time constant L R 40 ms at U 48 110 220 V DC 0 5 A 0 1 A 0 04 A Minimum contact load 100 mA at 24 V AC DC Table 13 Power output relays without TCS function Description Value Rated voltage 250 V AC DC Continuous contact carry 8 A Make and carry for 3 0 s 15 A Make...

Page 22: ...alue mA outputs Output range 20 mA 20 mA Operation accuracy 0 2 mA Maximum including wiring resistance 700 Ω Hardware response time 80 ms Isolation 4 kV Table 16 Ethernet interfaces Ethernet interface Protocol Cable Data transfer rate LAN1 X1 TCP IP protocol Fibre optic cable with LC connector or shielded twisted pair CAT 5e cable or better 100 MBits s Table 17 Fibre optic communication link Wave ...

Page 23: ...0 Rear side connection terminals IP 20 Table 21 Degree of protection of the LHMI Description Value Front and side IP 42 Table 22 Environmental conditions Description Value Operating temperature range 25 55ºC continuous Short time service temperature range 40 85ºC 16h Note Degradation in MTBF and HMI performance outside the temperature range of 25 55ºC Relative humidity 93 non condensing Atmospheri...

Page 24: ...t 55ºC 16 h at 85ºC IEC 60068 2 2 Cold test 96 h at 25ºC 16 h at 40ºC IEC 60068 2 1 Damp heat test cyclic 6 cycles at 25 55 C Rh 93 IEC 60068 2 30 Storage test 96 h at 40ºC 96 h at 85ºC IEC 60068 2 48 Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 24 ABB ...

Page 25: ...6 level 3 Radiated pulse modulated 10 V m rms f 900 MHz ENV 50204 IEC 60255 22 3 Radiated amplitude modulated 10 V m rms f 80 2700 MHz IEC 61000 4 3 IEC 60255 22 3 level 3 Fast transient disturbance tests IEC 61000 4 4 IEC 60255 22 4 class A All ports 4 kV Surge immunity test IEC 61000 4 5 IEC 60255 22 5 Communication 1 kV line to earth Binary inputs voltage inputs 2 kV line to earth 1 kV line to ...

Page 26: ...100 ms 60 1000 ms 95 5000 ms IEC 61000 4 11 Electromagnetic emission tests EN 55011 class A IEC 60255 25 Conducted RF emission mains terminal 0 15 0 50 MHz 79 dB µV quasi peak 66 dB µV average 0 5 30 MHz 73 dB µV quasi peak 60 dB µV average Radiated RF emission 30 230 MHz 40 dB µV m quasi peak measured at 10 m distance 230 1000 MHz 47 dB µV m quasi peak measured at 10 m distance Transformer Protec...

Page 27: ...MΏ 500 V DC Protective bonding resistance IEC 60255 27 Resistance 0 1 Ώ 4 A 60 s Table 26 Mechanical tests Description Reference Requirement Vibration tests sinusoidal IEC 60068 2 6 test Fc IEC 60255 21 1 Class 1 Shock and bump test IEC 60068 2 27 test Ea shock IEC 60068 2 29 test Eb bump IEC 60255 21 2 Class 1 Seismic test IEC 60255 21 3 method A Class 1 Table 27 Product safety Description Refere...

Page 28: ...ce EMC directive 2004 108 EC Standard EN 50263 2000 EN 60255 26 2007 Table 29 RoHS compliance Description Complies with RoHS directive 2002 95 EC Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 28 ABB ...

Page 29: ...tardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppression of harmonics RMS No suppression DFT 50 dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression P to P backup No suppression 1 Set Operate delay time 0 02 s Operate curve type IEC definite time Measurement mo...

Page 30: ...5 Operate delay time PHLPTOC 0 04 200 00 s 0 01 PHHPTOC 0 02 200 00 s 0 01 PHIPTOC 0 02 200 00 s 0 01 Operating curve type1 PHLPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 PHHPTOC Definite or inverse time Curve type 1 3 5 9 10 12 15 17 PHIPTOC Definite time 1 For further reference please refer to the Operating characteristics table Transformer Protection an...

Page 31: ...n time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms3 Suppression of harmonics RMS No suppression DFT 50 dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression P to P backup No suppression 1 Measurement mode default depends of stage current before fault 0 0 x In fn 50 Hz fault cur...

Page 32: ...0 s 0 01 Directional mode DPHxPDOC 1 Non directional 2 Forward 3 Reverse Characteristic angle DPHxPDOC 179 180 deg 1 Operating curve type1 DPHLPDOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 DPHHPDOC Definite or inverse time Curve type 1 3 5 9 10 12 15 17 1 For further reference refer to the Operating characteristics table Transformer Protection and Control 1M...

Page 33: ...ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppression of harmonics RMS No suppression DFT 50 dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression 1 Operate curve type IEC definite time Measurement mode default depends on stage current before fault 0 0 x In fn 50 Hz earth faul...

Page 34: ...rate delay time EFLPTOC 0 04 200 00 s 0 01 EFHPTOC 0 02 200 00 s 0 01 EFIPTOC 0 02 200 00 s 0 01 Operating curve type1 EFLPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 EFHPTOC Definite or inverse time Curve type 1 3 5 9 10 12 15 17 EFIPTOC Definite time 1 For further reference please refer to the Operating characteristics table Transformer Protection and Con...

Page 35: ...s Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppression of harmonics RMS No suppression DFT 50 dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression 1 Set Operate delay time 0 06 s Operate curve type IEC definite time Measurement mode default depends on stage current before fault...

Page 36: ...5 Operate delay time DEFLPDEF 0 06 200 00 s 0 01 DEFHPDEF 0 06 200 00 s 0 01 Operating curve type1 DEFLPDEF Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 DEFHPDEF Definite or inverse time Curve type 1 3 5 15 17 Operation mode DEFLPDEF and DEFHPDEF 1 Phase angle 2 IoSin 3 IoCos 4 Phase angle 80 5 Phase angle 88 1 For further reference refer to the Operating charac...

Page 37: ...nite time mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Current before fault 0 0 In fn 50 Hz 2 Includes the delay of the signal output contact Table 39 Stabilized restricted earth fault protection LREFPNDF main settings Parameter Function Value Range Step Operate value LREFPNDF 5 50 1 Restraint mode LREFPNDF None 2nd harmonic Start value 2 H LREF...

Page 38: ...Typical 0 96 Retardation time 60 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms 1 Current before fault 0 0 In fn 50 Hz 2 Includes the delay of the signal output contact Table 41 High impedance based restricted earth fault protection HREFPDIF main settings Parameter Function Value Range Step Operate value HREFPDIF 0 5 50 0 0 1 Minimum operate time HREFPDIF 0 020 300 00...

Page 39: ...2 3 4 5 1 Operate curve type IEC definite time negative sequence current before fault 0 0 fn 50 Hz 2 Includes the delay of the signal output contact 3 Maximum Start value 2 5 In Start value multiples in range of 1 5 to 20 Table 43 Negative sequence overcurrent protection NSPTOC main settings Parameter Function Value Range Step Start value NSPTOC 0 01 5 00 pu 0 01 Time multiplier NSPTOC 0 05 15 00 ...

Page 40: ...ue Range Step Temperature rise T2PTTR 0 0 200 0 deg 0 1 Max temperature T2PTTR 0 0 200 0 deg 0 1 Operate temperature T2PTTR 80 0 120 0 0 1 Weighting factor p T2PTTR 0 00 1 00 0 01 Short time constant T2PTTR 60 60000 s 1 Current reference T2PTTR 0 05 4 00 pu 0 01 Table 46 Three phase current inrush detection INRPHAR Characteristic Value Operation accuracy At the frequency f fn Current measurement 1...

Page 41: ...ccuracy At the frequency f fn 1 5 of the set value or 0 002 In Operate time1 2 Biased low stage Instantaneous high stage Typical 35 ms 5 ms Typical 17 ms 5 ms Reset time 30 ms Reset ratio Typical 0 96 Retardation time 35 ms Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 1 Differential current before fault 0 0 In fn 50 Hz Injected differential current 2 0 set operate value 2 Include...

Page 42: ...ion 2 TR2PTDF 10 50 1 End section 2 TR2PTDF 100 500 1 Start value 2 H TR2PTDF 7 20 1 Start value 5 H TR2PTDF 10 50 1 Winding 1 type TR2PTDF Y YN D Z ZN Winding 2 type TR2PTDF Y YN D Z ZN Zro A elimination TR2PTDF Not eliminated Winding 1 Winding 2 Winding 1 and 2 Clock number TR2PTDF Clk Num 0 Clk Num 1 Clk Num 2 Clk Num 4 Clk Num 5 Clk Num 6 Clk Num 7 Clk Num 8 Clk Num 10 Clk Num 11 Transformer P...

Page 43: ...Un Voltage before fault 0 9 Un fn 50 Hz overvoltage in one phase to phase with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact 3 Maximum Start value 1 20 Un Start value multiples in range of 1 10 to 2 00 Table 51 Three phase overvoltage protection PHPTOV main settings Parameter Function Value Range Step Start value PHPTOV 0 05 1 60 pu 0 01 Time ...

Page 44: ...Un Voltage before fault 1 1 Un fn 50 Hz undervoltage in one phase to phase with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact 3 Minimum Start value 0 50 Un Start value multiples in range of 0 90 to 0 20 Table 53 Three phase undervoltage protection PHPTUV main settings Parameter Function Value Range Step Start value PHPTUV 0 05 1 20 pu 0 01 Tim...

Page 45: ...0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 1 Positive sequence voltage before fault 0 0 x Un fn 50 Hz positive sequence overvoltage of nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact Table 55 Positive sequence overvoltage protection PSPTOV main settings Parameter Function Value Range Step Start val...

Page 46: ...sion of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Residual voltage before fault 1 1 Un fn 50 Hz residual voltage with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact Table 57 Positive sequence undervoltage protection PSPTUV main settings Parameter Function Value Range Step Start value PSPTUV 0 010 1 200 pu 0 001 Operate delay time PSPTUV 0...

Page 47: ... mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Residual voltage before fault 0 0 Un fn 50 Hz residual overvoltage with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact Table 59 Negative sequence overvoltage protection NSPTOV main settings Parameter Function Value Range Step Start value NSPTOV 0 ...

Page 48: ...ct Table 61 Residual overvoltage protection ROVPTOV main settings Parameter Function Value Range Step Start value ROVPTOV 0 010 1 000 pu 0 001 Operate delay time ROVPTOV 0 040 300 000 s 0 001 Table 62 Frequency gradient protection DAPFRC Characteristic Value Operation accuracy df dt 10 Hz s 10 mHz s Undervoltage blocking 1 5 of the set value or 0 002 Un Start time1 2 Start value 0 05 Hz s df dtFAU...

Page 49: ...50 Hz 2 Includes the delay of the signal output contact Table 65 Overfrequency protection DAPTOF main settings Parameter Function Value Range Step Start value DAPTOF 35 0 64 0 Hz 0 1 Operate delay time DAPTOF 0 170 60 000 s 0 001 Table 66 Underfrequency protection DAPTUF Characteristic Value Operation accuracy At the frequency f 35 to 66 Hz 0 003 Hz Start time1 2 fFault 0 99 set Start value Typica...

Page 50: ...time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 50 ms 1 Results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact Table 69 Overexcitation protection OEPVPH main settings Parameter Function Values Range Step Leakage React OEPVPH 0 0 50 0 0 1 Start value...

Page 51: ...results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact Table 71 Three phase underimpedance protection UZPDIS main settings Parameter Function Values Range Step Polar reach UZPDIS 1 6000 1 Operate delay time UZPDIS 0 04 200 00 0 01 Table 72 Circuit breaker failure protection CCBRBRF Characteristic Value Operation accuracy At the frequency f ...

Page 52: ...rip time CCBRBRF 0 00 60 00 s 0 01 CB failure delay CCBRBRF 0 00 60 00 s 0 01 CB fault delay CCBRBRF 0 00 60 00 s 0 01 Table 74 Multipurpose analog protection MAPGAPC Characteristic Value Operate time accuracy 1 0 of the set value or 20 ms Table 75 Multipurpose analog protection MAPGAPC main settings Parameter Function Values Range Step Operation mode MAPGAPC 1 2 1 Start value MAPGAPC 10000 0 1000...

Page 53: ...rating curve type voltage protection 5 ANSI Def Time 15 IEC Def Time 17 Inv Curve A 18 Inv Curve B 19 Inv Curve C 20 Programmable 21 Inv Curve A 22 Inv Curve B 23 Programmable Control functions Table 77 Synchrocheck SYNCRSYN Characteristic Value Operation accuracy At the frequency f fn Voltage 1 0 or 0 002 x Un Frequency 10 mHz Phase angle 2 Reset time 50 ms Reset ratio Typical 0 96 Operate time a...

Page 54: ... time mode 2 1 0 of the set value or 0 11 seconds Operate time accuracy in inverse time mode 3 15 0 of the set value or 0 15 s at theoretical B in range of 1 1 5 0 Also note fixed minimum operate time IDMT 1 s Reset ratio for control operation Typical 0 80 1 20 Reset ratio for analogue based blockings except run back raise voltage blocking Typical 0 96 1 04 1 Default setting values used 2 Default ...

Page 55: ...k lower voltage OLATCC 0 10 1 20 0 01 Runback raise V OLATCC 0 80 1 60 0 01 Cir current limit OLATCC 0 10 5 00 0 01 LDC limit OLATCC 0 00 2 00 0 01 Lower block tap OLATCC 36 36 1 Raise block tap OLATCC 36 36 1 LDC enable OLATCC FALSE TRUE Auto parallel mode OLATCC Master Follower NRP MCC 1 Band center voltage OLATCC 0 000 2 000 0 001 Line drop V Ris OLATCC 0 0 25 0 0 1 Line drop V React OLATCC 0 0...

Page 56: ...0 ms Traveling time measurement 10 ms Table 81 Fuse failure supervision SEQRFUF Characteristic Value Operation accuracy At the frequency f fn Current 1 5 of the set value or 0 002 In Voltage 1 5 of the set value or 0 002 Un Operate time1 NPS function UFault 1 1 x set Neg Seq voltage Lev UFault 5 0 x set Neg Seq voltage Lev Typical 35 ms 15 ms Typical 25 ms 15 ms Delta function ΔU 1 1 x set Voltage...

Page 57: ...tion Value Response time for binary inputs Typical 100 ms Table 86 Energy monitoring EPDMMTR Characteristic Value Operation accuracy At all three currents in range 0 10 1 20 x Inn At all three voltages in range 0 50 1 15 x Un At the frequency f fn Active power and energy in range PF 0 71 Reactive power and energy in range PF 0 71 1 5 for energy Suppression of harmonics DFT 50dB at f n x fn where n...

Page 58: ...rmonics DFT 50dB at f n fn where n 2 3 4 5 RMS No suppression Table 90 Three phase voltage measurement VPHMMXU Characteristic Value Operation accuracy At the frequency f fn 0 5 or 0 002 x Un at voltages in the range of 0 01 1 15 Un Suppression of harmonics DFT 50dB at f n fn where n 2 3 4 5 RMS No suppression Table 91 Residual current measurement RESCMMXU Characteristic Value Operation accuracy At...

Page 59: ...e power and energy in range PF 0 71 1 5 for power S P and Q 0 015 for power factor Suppression of harmonics DFT 50dB at f n x fn where n 2 3 4 5 Table 94 Sequence current CSMSQI Characteristic Value Operation accuracy At the frequency f fn 1 0 or 0 002 x In at currents in the range of 0 01 4 00 x In Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 Table 95 Sequence voltage VSMSQI Cha...

Page 60: ...ted measurement values and busbar arrangements GUID 5CFD3446 A92F 4A5F B60D 90025DCFDC61 V2 EN Figure 4 Local user interface 21 Mounting methods By means of appropriate mounting accessories the standard IED case for the 630 series IEDs can be flush mounted semi flush mounted or wall mounted Detachable HMI is intended for optimized mounting in medium voltage metal clad switchgear thus reducing wiri...

Page 61: ...F V1 EN Figure 5 Flush mounting GUID AF1BEC0B A9DC 4E9B 9C89 98F28B1C81DB V1 EN Figure 6 Semi flush mounting 252 5 270 ø6 8 180 101 6 13 366 GUID 945D3C86 A432 4C1F 927A A208E0C1F5F6 V2 EN Figure 7 Wall mounting 224 265 9 220 25 5 177 258 6 13 GUID A368C5C3 D4A9 40B7 BD0E 181A6BB7ECA6 V1 EN Figure 8 6U half 19 unit wall mounted with two mounting brackets and detached LHMI Transformer Protection an...

Page 62: ...d software modules of the IED Use the ordering key information in tables to generate the order number when ordering protection and control IEDs T B T BABAE B B B Z EANAX B DESCRIPTION 1 IED 630 series IED 4U half 19 housing S 630 series IED 6U half 19 housing T 630 series IED 4U half 19 housing with connector set U 630 series IED 6U half 19 housing with connector set V 2 Standard IEC B 3 Main appl...

Page 63: ...2 BI 27 BO BA 7 I I0 1 5A 3U 8 mA in RTD 4 mA out AD 1 41 BI 36 BO BB 8 I I0 1 5A 2U 8 mA in RTD 4 mA out AE 1 3 50 BI 45 BO BC 7 I I0 1 5A 1 I I0 0 1 0 5A 2U 8 mA in RTD 4 mA out 1 Binary input output options AD and AE require 6U half 19 IED housing digit 1 T or V 2 Binary input output option AC is not available for 4U high variant digit 1 S or U with RTD input options digit 5 6 BA BB or BC 3 Bin...

Page 64: ...Ethernet 100BaseFX LC A Ethernet 100BaseTX RJ 45 B 11 Communication protocol IEC 61850 A IEC 61850 and DNP3 TCP IP B IEC 61850 and IEC 60870 103 C GUID D74AEC37 E74D 4DE6 B586 008C9A763DDA V1 EN Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 64 ABB ...

Page 65: ...ce and over excitation protections C All options Z None N 15 Option 2 2 Automatic voltage regulator B Under impedance protection C Over excitation protection D None N 16 Power supply 48 125 V DC A 110 250 V DC 100 240 V AC B 17 Vacant digit Vacant X 18 Version Version 1 1 B 1 Integrated HMI is not available for 6 U high variant digit 1 T or V 2 Any optional function can be chosen only once Due to ...

Page 66: ...it cabling to the front for one 4U half 19 housing IED 1KHL400449R0001 19 rack mounting kit for one 4U half 19 housing IED 1KHL400236R0001 19 rack mounting kit for two 4U half 19 housing IEDs 1KHL400237R0001 Overhead ceiling mounting kit with cable space for one 4U half 19 housing IED 1KHL400450R0001 Wall mounting kit for direct rear wall mounting with cabling to the front of one 6U half 19 housin...

Page 67: ...6U housing IED including analog input variant 8I 2U 2RCA023040 Table 99 Optional cables for external display module Items Order number LHMI cable 1m 2RCA025073P0001 LHMI cable 2m 2RCA025073P0002 LHMI cable 3m 2RCA025073P0003 LHMI cable 4m 2RCA025073P0004 LHMI cable 5m 2RCA025073P0005 25 Tools The IED is delivered either with or without an optional factory made preconfiguration The default paramete...

Page 68: ... read and write access by means of PCM600 or the local HMI The IED connectivity package is a collection of software and specific IED information which enable system products and tools to connect and interact with the IED The connectivity packages reduce the risk of errors in system integration minimizing device configuration and set up times Table 100 Tools Configuration and setting tools Version ...

Page 69: ...tion in utility and industrial power systems To facilitate and streamline the system engineering ABB s IEDs are supplied with Connectivity Packages containing a compilation of software and IED specific information including single line diagram templates manuals a full IED data model including event and parameter lists By utilizing the Connectivity Packages the IEDs can be readily configured via th...

Page 70: ... bay solutions To enhance personnel safety the web HMI also enables remote access to substation devices and processes Furthermore COM600 can be used as a local data warehouse for technical documentation of the substation and for network data collected by the IEDs The collected network data facilitates extensive reporting and analyzing of network fault situations using the data historian and event ...

Page 71: ... Terminal diagrams GUID 3901C29E BCA6 44AE B6BC B2FA10958F19 V1 EN Figure 10 Terminal diagram for RET630 Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 ABB 71 ...

Page 72: ...GUID 5E27DD50 FD15 4824 BDFB DD52E29730EA V1 EN Figure 11 630 series BIO module option Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 72 ABB ...

Page 73: ...GUID CB7B1CF8 A0E4 42F5 998C 701641515127 V1 EN Figure 12 630 series RTD module option Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 ABB 73 ...

Page 74: ...b page contains the latest product documentation such as technical reference manual installation manual operators manual etc The selection tool on the web page helps you find the documents by the document category and language The Features and Application tabs contain product related information in a compact format GUID 08D3B177 E4DA 4CCF 81A0 017F639B9C5C V1 EN Figure 13 Product page Transformer ...

Page 75: ...arth fault low stage DEFLPDEF I0 67N 1 Directional earth fault high stage DEFHPDEF I0 67N 2 Stabilised restricted earth fault LREFPNDF dI0Lo 87NL High impedance based restricted earth fault protection HREFPDIF dI0Hi 87NH Negative sequence overcurrent NSPTOC I2 46 Three phase thermal overload for transformers T2PTTR 3Ith T 49T Three phase current inrush detection INRPHAR 3I2f 68 Transformer differe...

Page 76: ...3 Circuit breaker disconnector control GNRLCSWI I O CB DC I O CB DC Circuit breaker DAXCBR I O CB I O CB Disconnector DAXSWI I O DC I O DC Local remote switch interface LOCREM R L R L Synchrocheck SYNCRSYN SYNC 25 Tap changer control with voltage regulator OLATCC COLTC 90V Generic process I O Single point control 8 signals SPC8GGIO Double point indication DPGGIO Single point indication SPGGIO Gene...

Page 77: ...pe Residual current measurement RESCMMXU I0 I0 Residual voltage measurement RESVMMXU U0 Vn Power monitoring with P Q S power factor frequency PWRMMXU PQf PQf Sequence current measurement CSMSQI I1 I2 I1 I2 Sequence voltage measurement VSMSQI U1 U2 V1 V2 Disturbance recorder function Analog channels 1 10 samples A1RADR ACH1 ACH1 Analog channels 11 20 samples A2RADR ACH2 ACH2 Analog channels 21 30 c...

Page 78: ...e receive GOOSEMVRCV Single point receive GOOSESPRCV 30 Document revision history Document revision date Product version History A 2009 10 26 1 0 First release B 2009 12 23 1 0 Content updated C 2011 02 23 1 1 Content updated to correspond to the product version D 2011 05 18 1 1 Content updated Transformer Protection and Control 1MRS756978 D RET630 Product version 1 1 Issued 2011 05 18 78 ABB ...

Page 79: ...79 ...

Page 80: ...Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 www abb com substationautomation 1MRS756978 D Copyright 2011 ABB All rights reserved ...

Reviews: