4.1.2
Logging off
The user is automatically logged off after the display timeout. The IED returns to a
state where only reading is enabled. Manual logoff is also possible.
1.
Press
.
2.
To confirm logoff, select
Yes
and press
.
A071188 V2 EN
Figure 15:
Logging off
•
To cancel logoff, press
.
4.1.3
Turning the display backlight on
The display backlight is normally off. It turns on at power up.
•
To turn on the backlight manually, press any LHMI push button.
The backlight turns on and the panel is ready for further operations.
If the panel has not been used for a predefined timeout period, the backlight is
switched off. The user is logged out from the current user level after the display
backlight has turned off. The factory default for display timeout is 60 minutes.
The display returns to the default view and all unconfirmed operations, for example
parameter editing and breaker selection are cancelled.
Change the backlight timeout period in
Main menu/
Configuration/HMI/LHMI/DisplayTimeout
.
4.1.4
Selecting local or remote use
The control position of the protection relay can be changed with the R/L button. In
local position primary equipment, such as circuit breakers or disconnectors, can be
controlled via the LHMI. In remote position, control operations are possible only from
a higher level, that is from a control center.
•
Press
.
•
When the L LED is lit, local control is enabled and remote control disabled.
•
When the R LED is lit, remote control is enabled and local control disabled.
•
When neither of the LEDs is lit, both control positions are disabled.
1MRS756509 E
Section 4
Using the HMI
630 series
35
Operation Manual