An SCD file can be imported to a project only once. If another
IED needs to be later added to the configuration, it must be first
created with the
Create New IED
function. Import the related
CID or ICD file with the
Update IED
function. Another
alternative is to create a new project in IET600, and to import the
whole SCD file from PCM600 again. All existing IEC 61850
configuration including GOOSE remains if the changes made in
IET600 are already imported to PCM600.
If IED configuration has been changed in PCM600 after
importing the SCD file to IET600, the project can be updated
using
Update IED
function in IET600. The function first
compares the IET600 project and the selected SCL file, and
removes the old content of the updated IED(s) and creates new
IED content based on the updated file.
•
Export the SCD file for PCM600 by clicking the
Export
button.
In IET600 there is no need for manual data flow updates, since IET600 updates
all related data automatically while working with different editors.
7.7.2
Adding new IEC 61850 clients for IET600
IED SCL export from PCM600 for 630 series preconfigurations contains five default
client definitions, “Client1”...”Client5”, which are used by all the RCBs. For example
MicroSCADA and COM600 clients are able to use these client definitions directly. If
other clients need to be added to the IET600 project, the ICD file describing the client
data model has to be imported.
Adding a new IEC 61850 client to an IET600 project is a two-step operation. The
client must be first created using the
Create New IED
function, after which the
Update IED
function can be used to import the related ICD or CID file.
1.
To create an IED, click the
IEDs
tab in the navigation pane.
2.
Click the root node in the IED tree.
3.
Right-click the node and click
Create New IED
.
4.
Type the name of the client IED as it is in the file to be imported. Click
OK
.
5.
Right-click the created IED and click
Update IED
.
6.
Select any valid SCL file that is SCD, ICD, CID or IID, and click
Open
from the
file selection dialog box.
IET600 automatically matches IEDs with the same name in IET600 and in the
file.
7.
To import the IED from the file, click
OK
.
Section 7
1MRS756800 F
IEC 61850 communication engineering
114
630 series