The procedure used in configuring IEC 61850 clients can be used to
create or update any IED, also several IEDs at the same time.
7.7.3
Attaching IEC 61850 clients to a bus with IET600
All IEDs and report clients must be connected to a subnetwork to enable proper
configuration. For example after creating a new IEC 61850 client it must be manually
attached to a subnetwork.
1.
Click the
Communication
tab in the navigation pane.
2.
Click the
Subnetworks
tab in the editor pane.
3.
In the Subnetworks grid, select the bus from the Subnetwork list to attach the
IEC 61850 client to the bus.
An alternative way is to drag the client in the
Communication
tab to the correct
subnetwork.
7.7.4
IET600 user interface
IET600 user interface is divided into sections, that is, panes for navigating and
displaying the project data.
1MRS756800 F
Section 7
IEC 61850 communication engineering
630 series
115
Engineering Manual