10.2.7
Changed functions
Table 4:
Functions changed in the configuration after the migration from 630 series Ver. 1.0 to
630 series Ver. 1.1
Function
Implication
SCILO
1)
All instances are removed from ACT.
SPGGIO
1)
All instances are removed from ACT.
DPGGIO
1)
All instances are removed from ACT.
PSM_BATSUP
1)
The function is removed from the Application Configuration tool. The signal is now
available in the PSM module analog inputs.
PSM_TCS
1)
The function is removed from the Application Configuration tool. The signal is now
available in the PSM module analog inputs.
A3RADR
1)
The function is removed from the Application Configuration tool. The signal is now
available in the PSM module analog inputs.
DEFLPDEF
New setting Base value Sel phase added.
DEFHPDEF
New setting Base value Sel phase added.
INTRPTEF
Setting Ground start value renamed to Voltage start value.
SCEFRFLO
Amount of recorded data banks increased.
DARREC
CB closed Pos status setting default value changed to 0.
DSTPDIS
Setting Voltage Mem time added.
CVRSOF
Minimium values for Operate time delay, Dead line time and Cur voltage Det time
and step resolution for all time settings.
MNSPTOC
DO type corrected.
LREFPNDF
Removal of setting Base value Sel Res. Now internal minimum current levels are
also based on phase base values.
RESCPSCH
Harmonized default value for setting Scheme type with the default of the same
setting in DSOCPSCH.
GNRLCSWI
Changed default for input SYNC_OK to TRUE.
SSCBR
DOs PosOpn and PosCls removed from the default data set.
CSMSQI
The time quality for mandatory data SeqA.c3 (showing always zero amplitude) is
corrected.
VSMSQI
The time quality for mandatory data SeqV.c3 (showing always zero amplitude) is
corrected.
1) The function must always be reassigned if it has been used in the earlier configuration.
Table 5:
Functions changed in the configuration after the migration from 630 series Ver. 1.1 to
630 series Ver. 1.2
Function
Implication
EPDMMTR
1)
Function is removed from ACT.
COM
Debounce time lower limit changed for binary input.
BIO
Debounce time lower limit changed for binary input.
MAPGAPC
Under-operation mode corrected.
MNSPTOC
IEC and ANSI symbols updated.
Table continues on next page
Section 10
1MRS756800 F
Configuration migration
142
630 series