If the rear port is selected, type the correct IP address (of the physical IED
to be configured) to the
IP address
box.
Communication configuration is now defined.
IEC09000365-2-en.vsd
IEC09000365 V2 EN
Figure 12:
PCM600: Communication port and IP address
5.
Click
Next
in the
Configuration Wizard
.
6.
Cross-check that the IED whose IP address has been inserted has been detected
online by PCM600.
If the IED is not online or the IP address is not correct, data
cannot be scanned from the IED. Also, this prevents proceeding
further.
7.
Click
Scan
to scan/read the
IED Type
and
Product Version
for the IED that is
online.
After a successful scan, click
Next
.
1MRS756800 F
Section 4
Setting up a project
630 series
35
Engineering Manual