IED Compare
•
Communication Management
•
Configuration Migration
Download connectivity packages from the ABB Web site
http://www.abb.com/substationautomation
or directly with Update
Manager in PCM600.
2.2
Operation functionality
2.2.1
Product variants
The IED capabilities can be adjusted by selecting a product variant. The IED
capabilities can be extended by adding HW and/or SW options to the basic variant. For
example, the physical communication connector can be either an electrical or optical
Ethernet connector.
The number of binary inputs and outputs depends on the amount of the optional BIO
modules selected. For a 4U IED, it is possible to take 2 additional BIO modules at the
maximum, and for a 6U IED, it is possible to take 4 additional BIO modules at the
maximum.
•
Basic variant: 14 binary inputs and 9 binary outputs
•
With one optional BIO module: 23 binary inputs and 18 binary outputs
•
With two optional BIO modules: 32 binary inputs and 27 binary outputs
•
With three optional BIO modules: 41 binary inputs and 36 binary outputs
•
With four optional BIO modules: 50 binary inputs and 45 binary outputs
2.2.2
Optional functions
Some of the available functions are optional, that is, they are included in the delivered
product only when defined by the order code.
•
Transformer differential protection for two-winding transformers
•
Third-harmonic based stator earth-fault protection
2.3
Physical hardware
The mechanical design of the IED is based on a robust mechanical rack. The HW
design is based on the possibility to adapt the HW module configuration to different
customer applications.
Section 2
1MRS757582 C
REG630 overview
12
REG630
Application Manual