Attribute name
DATA type
Explanation
M/O/E
Health
ABB_c_dINS
Health
M
NamPlt
ABB_b_dLPL
Name plate
M
Control
Rs
ABB_v1_dSPC
Demand reset operation
E
Measurements
WhDmd
ABB_v2_dMV
Real energy demand
E
Status information
Alm
ABB_v1_dSPS
Maximum demand operate alarm
E
TmmDmdPer
ABB_v1_dINS
Time interval in seconds for demand
calculation
E
3.2.14
PSPTOC
Table 24:
PSPTOC
Attribute name
DATA type
Explanation
M/O/E
PTOC class
PTOC
Overcurrent based slow load shed of
power source
Data
Common logical node information
Mod
ABB_c_dINC
Mode
M
Beh
ABB_a_dINS
Behaviour
M
Health
ABB_c_dINS
Health
M
NamPlt
ABB_b_dLPL
Name plate
M
Control
Rs
ABB_v1_dSPC
Reset operation
E
Measurements
MaxA
ABB_v2_dMV
Maximum of three phase current of
source
E
OvLodTm
ABB_v2_dMV
Elapsed time
E
SetMaxA
ABB_v2_dMV
Current setting for overcurrent low
stage
E
TotOvLodTm
ABB_v2_dMV
Time require for overcurrent low stage
operate
E
Status information
Str
ABB_d_dACD
Start
M
Op
ABB_b_dACT
Operate
M
1MRS757261 E
Section 3
Logical node extensions
PML630/Compact Load-Shedding Solution
23
Point List Manual