3I> / I > BF
CCBRBRF
TRRET
TRBU
3I
START
POSCLOSE
51BF / 51NBF
CB_FAULT_AL
CB_FAULT
0
I0
BLOCK
BREAKER FAILURE PROTECTION
TRPPTRC(1)
TRIP
CL_LKOUT
BLOCK
OPERATE
RST_LKOUT
CB_OPEN_CMD
CBFP_RETRIP
COMMON OPERATE
1
2
TCS1
PO1
X327
MASTER TRIP
Open CB
CBFP BACKUP TRIP
X327
OR
OR
COMMON
OR
PSM
X304
6
10
COM
BI 08
CBFP_RETRIP
PSM
AVR Trip
Turbine trip
SO1
13
14
Common operate
COMMON OPERATE
SO2
X327
PSM
15
16
Common start
COMMON START
5
6
TCS3
PO3
Open CB
BI 07
9
OPERATE
COMMON OPERATE
TRPPTRC(2)
TRIP
CL_LKOUT
BLOCK
OPERATE
RST_LKOUT
COMMON OPERATE
CB CLOSE
GUID-2E7633C0-AA19-46E1-804B-24A6E1EE9825 V1 EN
Figure 17:
Tripping logic
3.2.6.18
Combined operate and start alarm signal
The operate outputs of all the protection functions (except for underpower protection),
and the external trip from AVR and turbine are combined in the OR-gate to get a
common Operate output. In addition, the activation of binary input COM101.BI12,
that is, the low pressure lockout will also trip the generator circuit breaker. This
common operate signal is connected to a tripping logic. It is also available as an alarm
binary output, PSM SO1, with a settable minimum alarm delay of 80 ms.
Similarly, a common Start output is derived from the start outputs of all the protection
functions (except for underpower protection) combined in an OR-gate. The output is
available as an alarm binary output PSM SO2 with a settable minimum alarm delay of
80 ms.
These combined operate and start signals are also connected to trigger the disturbance
recorder.
1MRS757582 C
Section 3
REG630 variants
REG630
43
Application Manual