Other IEDs also need update of incoming GOOSE signals from the
migrated IEDs in the Signal Matrix tool.
10.2.4
Updating DNP3 points in the Communication Management
tool
If DNP3 is used, the configured DNP3 points must be updated. All DNP3 points from
the migrated functions are removed from the configuration.
1.
Open the Communication Management tool.
Some of the earlier configured DNP3 points are struck through in the list.
2.
Select the signals on the left side corresponding to the struck-through signals.
3.
Click the blue arrow to the right to add the signals.
4.
Update the index numbers of the signals.
Updating is necessary to be able to keep the configuration in the DNP3 master
unchanged. The index number should match the one of the struck-through
signal.
5.
Remove the struck-through signals, when the update of signals is finished.
6.
Repeat the procedure for all signal types and all configured DNP3 masters (TCP
1-4).
•
Analog input objects
•
Binary input objects
•
Binary output objects
•
Counter object
•
Counter bit indication object
10.2.5
Mapping in Graphical Display Editor
•
In Graphical Display Editor, map all mappings to functions that have been
manually reinstantiated in the Application Configuration tool.
Map again all functions included in the Obsolete Functions and Hardware list of
the IED configuration migration report.
10.2.6
Updating Signal Matrix
•
Update connections between hardware and software functions.
•
Update connections of obsolete functions.
•
Update connections if a signal connected to hardware of a replaced function
has been removed or if its meaning has changed.
•
Verify and update the configuration if any of the changed functions has been
connected directly to hardware.
1MRS756800 F
Section 10
Configuration migration
630 series
141