Check the allowed minimum bending radius from the optical cable
manufacturer.
5.3.4.2
Wall mounting the main unit
GUID-1CABE0A1-790F-4773-9E4F-067D771F7226 v3
1.
Drill screw holes according to the dimensional drawing.
2.
Mount the mounting brackets using the required screws.
3.
Fit the main unit of IED securely between the mounting brackets by using the required
screws.
B
A
GUID-3451F22D-1B9E-47A1-A407-9D87B83AD837 V1 EN-US
Figure 11: 6U main unit and external LHMI display
A 241.1 mm 1 Screws
B 190.5 mm 2 Mounting brackets
The width of the 4U and 6U main units is 224 mm.
4.
Tighten the screws.
5.
Connect a cable to the RJ-45 connection on the front panel of the main unit to the
corresponding connection on external LHMI display module.