Section 7
Checking installation
7.1
Identifying hardware and software version
GUID-C5B48E09-7963-453C-B308-A52085B3F359 v1
Hardware and software version information can be found from the label that is attached on
the case of the IED. There is also module labels that can be used to identify modules inside the
IED.
7.2
Checking mounting
GUID-50578D7B-23D4-45B0-BB10-D3108EEF9B97 v1
Check that all fixing screws are tight and that all cables are connected.
7.3
Energizing the IED
GUID-11B42B1B-A6EF-4A04-81B1-1305066621F1 v6.1.1
Before you connect the auxiliary power, check that the terminal strip is wired and placed
correctly.
During the start-up all LEDs are lit for a short period.
•
Green Ready LED starts to flash
•
LCD lights up and starting... is displayed
•
The main menu is displayed. A steady green Ready LED indicates a successful start-up.
If the IED detects a diagnostic error during start-up, the green Ready LED flashes and the
internal fault code is displayed on the LCD.
Table 4:
Supervision Power Supply
Battery Supervision BATS
Logic
Led Battery
VS+ (output voltage)
Station Battery
Output Ready
VS+ Supervision
VS+ Output
Active
Active
1
On
> 15.1 V
> 33.5 V
Active
0
Off
< 14.6 V
> 33.5 V
Active
0
On
> 15.1 V
< 32.9 V
0
Off
< 14.6 V
< 32.9 V
1MRK 514 014-UEN A
Section 7
Checking installation
650 series
37
Installation manual