IEC08000338.vsd
IEC08000338 V1 EN
Figure 80:
CMT: Select Class window
9.3.1
Configuring DNP3 class
In DNP3 the user classifies the signals and defines those signals that are not member of
any class. CMT has a default predefined organization of classes per signal type. In the
master station the classes can be polled in sequences according to the demands in the
project. Unsolicited reporting is possible as well.
Modify the organization of the classes for each signal individually.
Procedure
1. Click in the
Class
field of the signal. A new window
Select Class
opens where the
user classifies the signal.
2. Select the signal classes and choose between
None
and
0
to
3
according to the
project demands.
3. Click
OK
to set the signal classification.
4. Write to IED.
Section 9
1MRK 511 245-UUS -
DNP3 communication engineering
114
650 series ANSI
Engineering Manual