DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
TmmRsLO
v2_dMV
mag.f
MX
-
TRESLO
Mon
Estimated time to reset of the function
(in min)
q
MX
-
TRESLO
Mon
Estimated time to reset of the function
(in min)
t
MX
-
TRESLO
Mon
Estimated time to reset of the function
(in min)
AClcPct
v2_dMV
mag.f
MX
-
I-MEASUR
Mon
Current measured by the function in %
of the rated current
q
MX
-
I-MEASUR
Mon
Current measured by the function in %
of the rated current
t
MX
-
I-MEASUR
Mon
Current measured by the function in %
of the rated current
TmpPct
v2_dMV
mag.f
MX
-
HEATCONT
Mon
Percentage of the heat content of the
transformer
q
MX
-
HEATCONT
Mon
Percentage of the heat content of the
transformer
t
MX
-
HEATCONT
Mon
Percentage of the heat content of the
transformer
7.5.16
Time undercurrent PTUC
7.5.16.1
Time delayed 2-step undercurrent protection UC2PTUC (37)
LN type
LN prefix LN class Function block name
PH3PTRC instance 1 (revision 1) PH3
PTRC
UC2PTUC (37)
PH3PTUC instance 1 (revision 0) PH3
PTUC
UC2PTUC (37)
PH3PTUC instance 2 (revision 0) PH3
PTUC
UC2PTUC (37)
UC2LLN0 instance 1 (revision 0) -
LLN0
UC2PTUC (37)
Table 91:
UC2PTUC (37) Logical node data (instance 1)
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Str
a_dACD
general
ST
-
RI
Mon
General pickup signal
dirGeneral
ST
-
-
Mon
Output for reporting the direction during
start
phsA
ST
-
-
Mon
Start signal for step 1 in L1
phsB
ST
-
-
Mon
Start signal for step 1 in L2
phsC
ST
-
-
Mon
Start signal for step 1 in L3
q
ST
-
RI
Mon
General pickup signal
Table continues on next page
Section 7
1MRK 511 281-UUS A
Logical node data model
134
650 series ANSI
Communication protocol manual
Summary of Contents for Relion 650 series ANSI
Page 1: ...Relion Protection and Control 650 series ANSI IEC 61850 Communication protocol manual ...
Page 2: ......
Page 13: ...Section 9 Glossary 227 Table of contents 650 series ANSI 7 Communication protocol manual ...
Page 14: ...8 ...
Page 26: ...20 ...
Page 44: ...38 ...
Page 226: ...220 ...
Page 241: ...235 ...