DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Beh
a_dINS
q
ST
-
Beh
Mon
Behaviour parameter for 61850
t
ST
-
Beh
Mon
Behaviour parameter for 61850
Str
b_dACD
general
ST
-
START
Mon
Start signal from accidental energizing
protection
q
ST
-
START
Mon
Start signal from accidental energizing
protection
t
ST
-
START
Mon
Start signal from accidental energizing
protection
Op
b_dACT
general
ST
T
TRIP
Mon
Trip signal from accidental energizing
protection
q
ST
T
TRIP
Mon
Trip signal from accidental energizing
protection
t
ST
T
TRIP
Mon
Trip signal from accidental energizing
protection
Armed
v1_dSPS
stVal
ST
-
ARMED
Mon
True when accidental energizing
protection is armed
q
ST
-
ARMED
Mon
True when accidental energizing
protection is armed
t
ST
-
ARMED
Mon
True when accidental energizing
protection is armed
7.5.21
Out-of-step protection PPAM
7.5.21.1
Out-of-step protection OOSPPAM (78)
LN type
LN prefix LN class Function block name
OOSPPAM (revision 1) OOS
PPAM
OOSPPAM (78)
Table 103:
OOSPPAM (78) Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
Oper.ctlVal
CO
-
-
Cmd
Mode parameter for 61850
Oper.origin.orCat
CO
-
-
Cmd
Mode parameter for 61850
Oper.origin.orIdent
CO
-
-
Cmd
Mode parameter for 61850
Oper.ctlNum
CO
-
-
Cmd
Mode parameter for 61850
Oper.T
CO
-
-
Cmd
Mode parameter for 61850
Oper.Test
CO
-
-
Cmd
Mode parameter for 61850
Oper.Check
CO
-
-
Cmd
Mode parameter for 61850
Table continues on next page
1MRK 511 281-UUS A
Section 7
Logical node data model
650 series ANSI
143
Communication protocol manual
Summary of Contents for Relion 650 series ANSI
Page 1: ...Relion Protection and Control 650 series ANSI IEC 61850 Communication protocol manual ...
Page 2: ......
Page 13: ...Section 9 Glossary 227 Table of contents 650 series ANSI 7 Communication protocol manual ...
Page 14: ...8 ...
Page 26: ...20 ...
Page 44: ...38 ...
Page 226: ...220 ...
Page 241: ...235 ...