DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
stVal
ST
-
-
Mon
Mode status value parameter for 61850
q
ST
-
-
Mon
Mode status value parameter for 61850
t
ST
-
-
Mon
Mode status value parameter for 61850
Beh
a_dINS
stVal
ST
-
Beh
Mon
Behaviour parameter for 61850
q
ST
-
Beh
Mon
Behaviour parameter for 61850
t
ST
-
Beh
Mon
Behaviour parameter for 61850
Str
b_dACD
general
ST
-
START
Mon
Set when measured impedance enters
lens characteristic
q
ST
-
START
Mon
Set when measured impedance enters
lens characteristic
t
ST
-
START
Mon
Set when measured impedance enters
lens characteristic
Op
b_dACT
general
ST
T
TRIP
Mon
Common trip, issued when either zone
1 or zone 2 give trip
q
ST
T
TRIP
Mon
Common trip, issued when either zone
1 or zone 2 give trip
t
ST
T
TRIP
Mon
Common trip, issued when either zone
1 or zone 2 give trip
Zn1SlpDet
v1_dSPS
stVal
ST
-
TRIPZ1
Mon
Zone 1 trip
q
ST
-
TRIPZ1
Mon
Zone 1 trip
t
ST
-
TRIPZ1
Mon
Zone 1 trip
Zn2SlpDet
v1_dSPS
stVal
ST
-
TRIPZ2
Mon
Zone 2 trip
q
ST
-
TRIPZ2
Mon
Zone 2 trip
t
ST
-
TRIPZ2
Mon
Zone 2 trip
Gen
v1_dSPS
stVal
ST
-
GENMODE
Mon
Generator rotates faster than the
system during pole slip
q
ST
-
GENMODE
Mon
Generator rotates faster than the
system during pole slip
t
ST
-
GENMODE
Mon
Generator rotates faster than the
system during pole slip
Mot
v1_dSPS
stVal
ST
-
MOTMODE
Mon
Generator rotates slower than the
system during pole slip
q
ST
-
MOTMODE
Mon
Generator rotates slower than the
system during pole slip
t
ST
-
MOTMODE
Mon
Generator rotates slower than the
system during pole slip
Section 7
1MRK 511 281-UUS A
Logical node data model
144
650 series ANSI
Communication protocol manual
Summary of Contents for Relion 650 series ANSI
Page 1: ...Relion Protection and Control 650 series ANSI IEC 61850 Communication protocol manual ...
Page 2: ......
Page 13: ...Section 9 Glossary 227 Table of contents 650 series ANSI 7 Communication protocol manual ...
Page 14: ...8 ...
Page 26: ...20 ...
Page 44: ...38 ...
Page 226: ...220 ...
Page 241: ...235 ...