Included in PCM600 is the new IEC61850 Configuration tool which allows the user
to define data sets and control blocks for both Client Server and GOOSE
communication.
•
The IEC61850 Configuration tool gives the user the possibility to make the
IEC61850 engineering without export / import step.
It does NOT however allow the User to define the substation part.
IET600:
•
Open a SCD file or import/merge a SCD, ICD or CID file for the particular IED(s).
•
For each IED, the user defines the datasets, the control blocks for reporting (this
means unbufffered/buffered reporting and GOOSE) and the properties for each
report control block.
Data sets (DS) are generated automatically in PCM600. Report
control blocks (RCBs) are not generated automatically in PCM600.
•
If client definitions (like client. ICD) are required in the system configuration, they
are merged into IET600 and connected to the unbuffered/buffered report control
blocks.
•
Logical nodes, which are not related to the conducting equipment, must be included
in the bay level in the substation section.
•
The resulting SCD file is exported from IET600.
PCM600:
Define the inputs for the client in IET600 and cross-reference the signals in SMT. Import
the SCD file to PCM600 to receive GOOSE data. For each IED that shall receive GOOSE
information, the received data is connected to the applications using SMT in PCM600.
If input signals are not defined for clients in IET600, they will not be
visible in SMT.
1MRK 511 281-UUS A
Section 3
Substation Configuration description Language (SCL)
650 series ANSI
31
Communication protocol manual
Summary of Contents for Relion 650 series ANSI
Page 1: ...Relion Protection and Control 650 series ANSI IEC 61850 Communication protocol manual ...
Page 2: ......
Page 13: ...Section 9 Glossary 227 Table of contents 650 series ANSI 7 Communication protocol manual ...
Page 14: ...8 ...
Page 26: ...20 ...
Page 44: ...38 ...
Page 226: ...220 ...
Page 241: ...235 ...