Section 5
Supported services
IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describes how the
services are applied in the communication. The conformance documents contain the
description of the supported services in the IED.
Services that are not mentioned in this chapter or in the conformance document are not
supported by the IED 650.
Data set
Define data sets by the SCD description.
Create data sets under LD0/LLN0.
The maximum number of data sets (DS) in an IED is 100. The maximum
number of data objects (DO) in a data set for MMS is 100. The maximum
data attributes (DA) in a data set for GOOSE is 150.
Substitution
Substitution is supported for the respective DATA, according to IEC 61850-7-4, that have
the substitution attributes defined.
Setting group control block
The task of changing setting groups is supported via the actSG data attribute.
There is only one setting group control block, which is located in LD0/LLN0 (Logical
Device/Logical Node 0).
Change or edit of setting values as well as reading of setting values is neither supported
nor visible in IEC 61850.
Note that the actual number of used setting groups is defined by the
parameter
MaxNoSetGRP
in the function
SETGRPS
, which is configured
in PST in PCM600.
Report control block
For properties about report control blocks, see PIXIT.
1MRK 511 281-UUS A
Section 5
Supported services
650 series ANSI
35
Communication protocol manual
Summary of Contents for Relion 650 series ANSI
Page 1: ...Relion Protection and Control 650 series ANSI IEC 61850 Communication protocol manual ...
Page 2: ......
Page 13: ...Section 9 Glossary 227 Table of contents 650 series ANSI 7 Communication protocol manual ...
Page 14: ...8 ...
Page 26: ...20 ...
Page 44: ...38 ...
Page 226: ...220 ...
Page 241: ...235 ...