IEC10000173.vsd
IEC10000173 V1 EN
Figure 74:
CMT: Hardware channels appearing in the Communication
Management Tool
2. Right-click the IED in the plant structure and select
Communication Management
to start the Communication management tool.
3. Select the DNP3 protocol from the new window and click
OK
the design of the two container windows, which open after the selection of DNP3.
•
The right window shows tabs for possible communication channels.
•
The left window has a drop down menu for signal selection and buttons for
signal movement, see
IEC08000337.vsd
IEC08000337 V1 EN
Figure 75:
CMT: Container window design when selecting DNP3 protocol
Procedure to move signals:
1. Select one or several signals.
•
Click in the list of signals to select one signal.
•
Press
Shift
or
Ctrl
and several signals to select a set of signals.
•
Right-click in the list of signals, select
Select All
from the context menu or
press
Ctrl+A
to select all signals.
2. Press the blue arrow button to insert the selected signals into the configuration.
3. Press the green double arrow button to insert all signals into the configuration, see
1MRK 511 245-UUS -
Section 9
DNP3 communication engineering
650 series ANSI
111
Engineering Manual