DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
InvPosChg
v1_dSPS
t
ST
-
INVALPOS
Mon
Last position change was an invalid
change
TapChgFlt
v1_dSPS
stVal
ST
-
TCERRAL
Mon
Alarm for none or illegal tap position
change
q
ST
-
TCERRAL
Mon
Alarm for none or illegal tap position
change
t
ST
-
TCERRAL
Mon
Alarm for none or illegal tap position
change
TapPosFlt
v1_dSPS
stVal
ST
-
POSERRAL
Mon
Alarm that indicates a problem with the
position indication
q
ST
-
POSERRAL
Mon
Alarm that indicates a problem with the
position indication
t
ST
-
POSERRAL
Mon
Alarm that indicates a problem with the
position indication
CLCnt
v2_dMV
mag.f
MX
-
CLCNT_VAL
Mon
Remaining number of operations at
rated load
q
MX
-
CLCNT_VAL
Mon
Remaining number of operations at
rated load
t
MX
-
CLCNT_VAL
Mon
Remaining number of operations at
rated load
7.13
Logical nodes for further power system equipment
7.13.1
Battery ZBAT
7.13.1.1
Station battery supervision SPVNZBAT
LN type
LN prefix LN class Function block name
SPVNZBAT (revision 0) SPVN
ZBAT
SPVNZBAT
Table 151:
SPVNZBAT Logical node data
DO name
DO type
DA name
FC
T
Signal
Mon/C
md
Description
Mod
a_dINC
Oper.ctlVal
CO
-
-
Cmd
Mode parameter for 61850
Oper.origin.orCat
CO
-
-
Cmd
Mode parameter for 61850
Oper.origin.orIdent
CO
-
-
Cmd
Mode parameter for 61850
Oper.ctlNum
CO
-
-
Cmd
Mode parameter for 61850
Oper.T
CO
-
-
Cmd
Mode parameter for 61850
Table continues on next page
Section 7
1MRK 511 281-UUS A
Logical node data model
218
650 series ANSI
Communication protocol manual
Summary of Contents for Relion 650 series ANSI
Page 1: ...Relion Protection and Control 650 series ANSI IEC 61850 Communication protocol manual ...
Page 2: ......
Page 13: ...Section 9 Glossary 227 Table of contents 650 series ANSI 7 Communication protocol manual ...
Page 14: ...8 ...
Page 26: ...20 ...
Page 44: ...38 ...
Page 226: ...220 ...
Page 241: ...235 ...