Binary input/output module, mA and time synchronization boards.
#11
Notes and Rules
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfills additional standards. As a consequence the EMC withstand
capability is further increased.
BIM with 30 mA inrush current is still available.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM included.
Slot position (rear view)
X31
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
Note: Max 3 positions in 1/2 rack
and 11 in 1/1 rack with 2 TRM
1/2 Case with 1 TRM
█
█
█
Note: Only for A20
1/1 Case with 2 TRM
█
█
█
█
█
█
█
█
█
█
█
Note: Only for B30/C30
No board in slot
X
X
X
X
X
X
X
X
X
X
X
Binary output module 24 output relays (BOM)
A
A
A
A
A
A
A
A
A
A
Note: Maximum 4 (BOM+SOM
+MIM) boards.
BIM 16 inputs, RL24-30 VDC, 50 mA
B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
B
1
BIM 16 inputs, RL48-60 VDC, 50 mA
C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
C
1
BIM 16 inputs, RL110-125 VDC, 50 mA
D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
D
1
BIM 16 inputs, RL220-250 VDC, 50 mA
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
E
1
BIM 16 inputs, 220-250 VDC, 120mA
E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
E
2
BIMp 16 inputs, RL24-30 VDC, 30 mA, for pulse counting
F
F
F
F
F
F
F
F
F
BIMp 16 inputs, RL48-60 VDC, 30 mA, for pulse counting
G
G
G
G
G
G
G
G
G
BIMp 16 inputs, RL110-125 VDC, 30 mA, for pulse counting
H
H
H
H
H
H
H
H
H
BIM 16 inputs, RL220-250 VDC, 30 mA, for pulse counting
K
K
K
K
K
K
K
K
K
IOM 8 inputs, 10+2 output, RL24-30 VDC, 50 mA
L1 L1
L1 L1 L1 L1 L1 L1 L1
IOM 8 inputs, 10+2 output, RL48-60 VDC, 50 mA
M
1
M
1
M
1
M
1
M
1
M
1
M
1
M
1
M
1
IOM 8 inputs, 10+2 output, RL110-125 VDC, 50 mA
N
1
N
1
N
1
N
1
N
1
N
1
N
1
N
1
N
1
IOM 8 inputs, 10+2 output, RL220-250 VDC, 50 mA
P
1
P
1
P
1
P
1
P
1
P
1
P
1
P
1
P
1
IOM 8 inputs 10+2 output relays, 220-250 VDC, 110mA
P
2
P
2
P
2
P
2
P
2
P
2
P
2
P
2
P
2
IOM with MOV 8 inputs, 10-2 output, 24-30 VDC, 30 mA
U
U
U
U
U
U
U
U
U
IOM with MOV 8 inputs, 10-2 output, 48-60 VDC, 30 mA
V
V
V
V
V
V
V
V
V
IOM with MOV 8 inputs, 10-2 output, 110-125 VDC, 30 mA
W
W
W
W
W
W
W
W
W
IOM with MOV 8 inputs, 10-2 output, 220-250 VDC, 30 mA
Y
Y
Y
Y
Y
Y
Y
Y
Y
mA input module MIM 6 channels
R
R
R
R
R
R
R
R
R
Note: MIM not in A20, Maximum
1 MIM board in 1/2 case.
SOM Static output module, 12 outputs, 48-60 VDC
T1 T1 T1 T1 T1 T1 T1 T1 T1 Note: SOM must not be placed in
the following positions: 1/2 case
slot X51, 1/1 case 2 TRM slot
X131
SOM static outputs module, 12 outputs, 110-250 VDC
T2 T2 T2 T2 T2 T2 T2 T2 T2
Selection for position #11.
1MRK 502 068-BEN D
Generator protection REG670 2.1 IEC
Product version: 2.1
ABB
125