Logic rotating switch for function selection and LHMI
presentation SLGAPC
SEMOD114908-4 v9
The logic rotating switch for function selection and LHMI
presentation SLGAPC (or the selector switch function block)
is used to get an enhanced selector switch functionality
compared to the one provided by a hardware selector switch.
Hardware selector switches are used extensively by utilities,
in order to have different functions operating on pre-set
values. Hardware switches are however sources for
maintenance issues, lower system reliability and an extended
purchase portfolio. The selector switch function eliminates all
these problems.
Selector mini switch VSGAPC
SEMOD158756-5 v7
The Selector mini switch VSGAPC function block is a
multipurpose function used for a variety of applications, as a
general purpose switch.
VSGAPC can be controlled from the menu or from a symbol
on the single line diagram (SLD) on the local HMI.
Generic communication function for Double Point indication
DPGAPC
SEMOD55850-5 v6
Generic communication function for Double Point indication
DPGAPC function block is used to send double indications to
other systems, equipment or functions in the substation
through IEC 61850-8-1 or other communication protocols. It
is especially used in the interlocking station-wide logics.
Single point generic control 8 signals SPC8GAPC
SEMOD176462-4 v8
The Single point generic control 8 signals SPC8GAPC
function block is a collection of 8 single point commands,
designed to bring in commands from REMOTE (SCADA) to
those parts of the logic configuration that do not need
extensive command receiving functionality (for example,
SCSWI). In this way, simple commands can be sent directly
to the IED outputs, without confirmation. Confirmation (status)
of the result of the commands is supposed to be achieved by
other means, such as binary inputs and SPGAPC function
blocks. The commands can be pulsed or steady with a
settable pulse time.
AutomationBits, command function for DNP3.0 AUTOBITS
SEMOD158591-5 v7
AutomationBits function for DNP3 (AUTOBITS) is used within
PCM600 to get into the configuration of the commands
coming through the DNP3 protocol. The AUTOBITS function
plays the same role as functions GOOSEBINRCV (for IEC
61850) and MULTICMDRCV (for LON).
Single command, 16 signals
M12446-6 v5
The IEDs can receive commands either from a substation
automation system or from the local HMI. The command
function block has outputs that can be used, for example, to
control high voltage apparatuses or for other user defined
functionality.
11. Logic
Tripping logic SMPPTRC
M12275-3 v10
A function block for protection tripping is always provided as
basic for each circuit breaker involved in the tripping of the
fault. It provides a settable pulse prolongation to ensure a trip
pulse of sufficient length, as well as all functionality necessary
for correct co-operation with autoreclosing functions.
The trip function block also includes a settable latch
functionality for evolving faults and breaker lock-out.
Trip matrix logic TMAGAPC
M15321-3 v11
The trip matrix logic TMAGAPC function is used to route trip
signals and other logical output signals to different output
contacts on the IED.
The trip matrix logic function has 3 output signals and these
outputs can be connected to physical tripping outputs
according to the specific application needs for settable pulse
or steady output.
Group alarm logic function ALMCALH
GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v3
The group alarm logic function ALMCALH is used to route
several alarm signals to a common indication, LED and/or
contact, in the IED.
Group warning logic function WRNCALH
GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v3
The group warning logic function WRNCALH is used to route
several warning signals to a common indication, LED and/or
contact, in the IED.
Group indication logic function INDCALH
GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v3
The group indication logic function INDCALH is used to route
several indication signals to a common indication, LED and/or
contact, in the IED.
Basic configurable logic blocks
M11396-4 v15
The basic configurable logic blocks do not propagate the time
stamp and quality of signals (have no suffix QT at the end of
their function name). A number of logic blocks and timers are
always available as basic for the user to adapt the
configuration to the specific application needs. The list below
shows a summary of the function blocks and their features.
These logic blocks are also available as part of an extension
logic package with the same number of instances.
• AND function block. Each block has four inputs and two
outputs where one is inverted.
• GATE function block is used for whether or not a signal
should be able to pass from the input to the output.
• INVERTER function block that inverts one input signal to
the output.
• LLD function block. Loop delay used to delay the output
signal one execution cycle.
1MRK 502 068-BEN D
Generator protection REG670 2.1 IEC
Product version: 2.1
ABB
29