IRIG-B Time synchronizing module
SEMOD141113-4 v7
The IRIG-B time synchronizing module is used for accurate
time synchronizing of the IED from a station clock.
The Pulse Per Second (PPS) input shall be used for
synchronizing when IEC 61850-9-2LE is used.
Electrical (BNC) and optical connection (ST) for 0XX and 12X
IRIG-B support.
Transformer input module TRM
M14875-3 v9
The transformer input module is used to galvanically separate
and adapt the secondary currents and voltages generated by
the measuring transformers. The module has twelve inputs in
different combinations of currents and voltage inputs. Either
protection class or metering class CT inputs are available.
Alternative connectors of Ring lug or Compression type can
be ordered.
High impedance resistor unit
M16727-3 v2
The high impedance resistor unit, with resistors for pick-up
value setting and a voltage dependent resistor, is available in
a single phase unit and a three phase unit. Both are mounted
on a 1/1 19 inch apparatus plate with compression type
terminals.
Layout and dimensions
IP14539-1 v1
Dimensions
IP14826-1 v1
M15243-4 v6
C
B
D
E
A
IEC08000163-2-en.vsd
IEC08000163 V2 EN-US
Figure 8.
Case with rear cover
xx08000165.vsd
J
G
F
K
H
IEC08000165 V1 EN-US
Figure 9.
Case with rear cover and 19” rack mounting kit
IEC06000182-2-en.vsd
IEC06000182 V2 EN-US
Figure 10.
A 1/2 x 19” size IED side-by-side with RHGS6.
M15243-12 v7
1MRK 502 068-BEN D
Generator protection REG670 2.1 IEC
Product version: 2.1
36