Maximum 176 binary input channels may
be activated simultaneously with influencing
factors within nominal range.
M12573-1 v8
Table 14. IOM - Binary input/output module
Quantity
Rated value
Nominal range
Binary inputs
8
-
DC voltage, RL
24/30 V
48/60 V
110/125 V
220/250 V
RL
±
20%
RL
±
20%
RL
±
20%
RL
±
20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency
10 pulses/s max
Oscillating signal discriminator
Blocking settable 1-40 Hz
Release settable 1-30 Hz
Debounce filter
Settable 1-20 ms
1MRK 502 068-BEN D
Generator protection REG670 2.1 IEC
Product version: 2.1
42
ABB