Table 23. Electromagnetic compatibility
Test
Type test values
Reference standards
1 MHz burst disturbance
2.5 kV
IEC 60255-26
100 kHz slow damped oscillatory wave immunity test
2.5 kV
IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz
2-4 kV
IEC 61000-4-12, Class IV
Surge withstand capability test
2.5 kV, oscillatory
4.0 kV, fast transient
IEEE/ANSI C37.90.1
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEC 60255-26
IEC 61000-4-2, Class IV
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.1
Fast transient disturbance
4 kV
IEC 60255-26, Zone A
Surge immunity test
2-4 kV, 1.2/50
m
s
high energy
IEC 60255-26, Zone A
Power frequency immunity test
150-300 V, 50 Hz
IEC 60255-26, Zone A
Conducted common mode immunity test
15 Hz-150 kHz
IEC 61000-4-16, Class IV
Power frequency magnetic field test
1000 A/m, 3 s
100 A/m, cont.
IEC 61000-4-8, Class V
Pulse magnetic field immunity test
1000 A/m
IEC 61000–4–9, Class V
Damped oscillatory magnetic field test
100 A/m
IEC 61000-4-10, Class V
Radiated electromagnetic field disturbance
20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-26
Radiated electromagnetic field disturbance
20 V/m
80-1000 MHz
IEEE/ANSI C37.90.2
Conducted electromagnetic field disturbance
10 V, 0.15-80 MHz
IEC 60255-26
Radiated emission
30-5000 MHz
IEC 60255-26
Radiated emission
30-5000 MHz
IEEE/ANSI C63.4, FCC
Conducted emission
0.15-30 MHz
IEC 60255-26
Table 24. Insulation
Test
Type test values
Reference standard
Dielectric test
2.0 kV AC, 1 min.
IEC 60255-27
ANSI C37.90
Impulse voltage test
5 kV, 1.2/50
m
s, 0.5 J
Insulation resistance
>100 M
W
at 500 VDC
1MRK 502 068-BEN D
Generator protection REG670 2.1 IEC
Product version: 2.1
48
ABB