![background image](http://html.mh-extra.com/html/abb/relion-670-series-reg670/relion-670-series-reg670_applications-manual_4795111.webp)
Table 12:
Trip LED (red)
LED state
Description
Off
Normal operation.
On
A protection function has tripped. An indication message is displayed if the
auto-indication feature is enabled in the local HMI.
The trip indication is latching and must be reset via communication, LHMI or
binary input on the LEDGEN component. To open the reset menu on the
LHMI, press
.
Flasing
Configuration mode.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual
alarm/status signal, connected to any of the LED function blocks, can be assigned to
one of the three LED colors when configuring the IED.
Table 13:
Alarm indications
LED state
Description
Off
Normal operation. All activation signals are off.
On
•
Follow-S sequence: The activation signal is on.
•
LatchedColl-S sequence: The activation signal is on, or it is off but the indication has
not been acknowledged.
•
LatchedAck-F-S sequence: The indication has been acknowledged, but the
activation signal is still on.
•
LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
•
LatchedReset-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
Flashing
•
Follow-F sequence: The activation signal is on.
•
LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
•
LatchedAck-S-F sequence: The indication has been acknowledged, but the
activation signal is still on.
5.4.2
Parameter management
GUID-5EE466E3-932B-4311-9FE1-76ECD8D6E245 v9
The LHMI is used to access the relay parameters. Three types of parameters can be
read and written.
•
Numerical values
•
String values
•
Enumerated values
1MRK 502 071-UUS A
Section 5
Local HMI
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
105
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...