For the
TripAngle
it is recommended to set this parameter to 90° to assure limited
stress for the circuit breaker.
In a power system it is desirable to split the system into predefined parts in case of pole
slip. The protection is therefore situated at lines where this predefined split shall take
place.
Normally the
N1Limit
is set to 1 so that the line will be tripped at the first pole slip.
If the line shall be tripped at all pole slip situations also the parameter
N2Limit
is set to
1. In other cases a larger number is recommended.
8.4.3.2
Setting example for generator application
SEMOD172162-90 v4
In case of out of step conditions this shall be checked if the pole slip centre is inside the
generator (zone 1) or if it is situated in the network (zone 2).
ZC
ZA
ZB
en07000017.vsd
IEC07000017 V1 EN-US
Figure 140:
Generator application of pole slip protection
If the apparent impedance crosses the impedance line ZB – ZA this is the detected
criterion of out of step conditions, see figure
.
Section 8
1MRK 502 071-UUS A
Impedance protection
290
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...