Figure 146:
The complex apparent power from the generator, at different angles δ
To prevent damages to the generator block, the generator should be tripped at low
excitation. A suitable area, in the PQ-plane, for protection operation is shown in
figure
. In this example limit is set to a small negative reactive power independent
of active power.
Section 8
1MRK 502 071-UUS A
Impedance protection
304
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual