The straight line in the PQ-diagram will be equivalent with a circle in the impedance
plane, see figure
. In this example the circle is corresponding to constant Q, that is,
characteristic parallel with P-axis.
R
X
Underexcitation
Protection Operation area
en06000452.vsd
IEC06000452 V2 EN-US
Figure 149:
The straight line in the PQ-diagram is equivalent with a circle in the
impedance plane
LEXPDIS (40) in the IED is realised by two impedance circles and a directional
restraint possibility as shown in figure
1MRK 502 071-UUS A
Section 8
Impedance protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
307
Application manual