V
ref
I
dir
ANSI09000636-1-en.vsd
1
2
2
3
4
ANSI09000636 V1 EN-US
Figure 172:
Directional function characteristic
1. RCA = Relay characteristic angle
2. ROA = Relay operating angle
3. Reverse
4. Forward
9.2.3.1
Settings for each step
M12982-19 v10
x
means step 1, 2, 3 and 4.
DirModeSelx
: The directional mode of step
x
. Possible settings are
Disabled
/
Non-
directional
/
Forward
/
Reverse
.
Section 9
1MRK 502 071-UUS A
Current protection
350
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062