may cause cavitations. The risk for damages to hydro turbines can justify reverse
power protection in unattended plants.
A hydro turbine that rotates in water with closed wicket gates will draw electric power
from the rest of the power system. This power will be about 10% of the rated power. If
there is only air in the hydro turbine, the power demand will fall to about 3%.
Diesel engines should have reverse power protection. The generator will take about
15% of its rated power or more from the system. A stiff engine may require perhaps
25% of the rated power to motor it. An engine that is well run in might need no more
than 5%. It is necessary to obtain information from the engine manufacturer and to
measure the reverse power during commissioning.
Gas turbines usually do not require reverse power protection.
Figure
illustrates the reverse power protection with underpower IED and with
overpower IED. The underpower IED gives a higher margin and should provide better
dependability. On the other hand, the risk for unwanted operation immediately after
synchronization may be higher. One should set the underpower IED to trip if the active
power from the generator is less than about 2%. One should set the overpower IED to
trip if the power flow from the network to the generator is higher than 1%.
Underpower IED
Overpower IED
Q
Q
P
P
Operating point
without
turbine torque
Margin
Margin
Operate
Line
Operate
Line
Operating point
without
turbine torque
IEC06000315-2-en.vsd
IEC06000315 V2 EN-US
Figure 198:
Reverse power protection with underpower IED and overpower IED
9.11.3
Setting guidelines
SEMOD172150-4 v7
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
VBase
and
SBase
as applicable.
Operation
: With the parameter
Operation
the function can be set
Enabled
/
Disabled
.
1MRK 502 071-UUS A
Section 9
Current protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
413
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...