989_OP = 1
•
989_CL = 0
•
989G_OP = 1
•
989G_CL = 0
If, in this case, line voltage supervision is added, then rather than setting 989 to open
state, specify the state of the voltage supervision:
•
989_OP = VOLT_OFF
•
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
•
VOLT_OFF = 1
•
VOLT_ON = 0
15.3.9
Interlocking for breaker-and-a-half diameter BH (3)
IP14173-1 v3
15.3.9.1
Application
M13570-3 v6
The interlocking for breaker-and-a-half diameter (BH_CONN(3), BH_LINE_A(3),
BH_LINE_B(3)) functions are used for lines connected to a breaker-and-a-half
diameter according to figure
.
Section 15
1MRK 502 071-UUS A
Control
594
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual