With the master-follower method
•
With the reverse reactance method
•
With the circulating current method
Of these alternatives, the first and the last require communication between the function
control blocks of the different transformers, whereas the middle alternative does not
require any communication.
The voltage control includes many extra features such as possibility to avoid
simultaneous tapping of parallel transformers, hot stand by regulation of a transformer
within a parallel group, with a LV CB open, compensation for a possible capacitor
bank on the LV side bay of a transformer, extensive tap changer monitoring including
contact wear and hunting detection, monitoring of the power flow in the transformer so
that for example, the voltage control can be blocked if the power reverses and so on.
The voltage control function is built up by two function blocks which both are logical
nodes in IEC 61850-8-1:
•
Automatic voltage control for tap changer, TR1ATCC (90) for single control and
TR8ATCC (90) for parallel control.
•
Tap changer control and supervision, 6 binary inputs, TCMYLTC (84) and 32
binary inputs, TCLYLTC (84)
Automatic voltage control for tap changer, TR1ATCC (90) or TR8ATCC (90) is a
function designed to automatically maintain the voltage at the LV-side side of a power
transformer within given limits around a set target voltage. A raise or lower command
is generated whenever the measured voltage, for a given period of time, deviates from
the set target value by more than the preset deadband value (degree of insensitivity). A
time delay (inverse or definite time) is set to avoid unnecessary operation during
shorter voltage deviations from the target value, and in order to coordinate with other
automatic voltage controllers in the system.
TCMYLTC and TCLYLTC (84)are an interface between the Automatic voltage control
for tap changer, TR1ATCC (90) or TR8ATCC (90) and the transformer load tap
changer itself. More specifically this means that it gives command-pulses to a power
transformer motor driven load tap changer and that it receives information from the
load tap changer regarding tap position, progress of given commands, and so on.
TCMYLTC and TCLYLTC (84) also serve the purpose of giving information about tap
position to the transformer differential protection.
Control location local/remote
SEMOD159053-30 v3
The tap changer can be operated from the front of the IED or from a remote place
alternatively. On the IED front there is a local remote switch that can be used to select
the operator place. For this functionality the Apparatus control function blocks Bay
1MRK 502 071-UUS A
Section 15
Control
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
597
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...