Application
SEMOD55350-5 v8
Generic communication function for Single Point Value (SPGAPC) function is used to
send one single logical output to other systems or equipment in the substation.
SP16GAPC can be used to send up to 16 single point values from the application
functions running in the same cycle time. SPGAPC has one visible input and
SPGAPC16 has 16 visible inputs that should be connected in the ACT tool.
Setting guidelines
SEMOD55376-5 v5
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
SEMOD55402-1 v3
Application
SEMOD55872-5 v10
Generic communication function for measured values (MVGAPC) function is used to
send the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
Setting guidelines
SEMOD55424-5 v5
The settings available for Generic communication function for Measured Value
(MVGAPC) function allows the user to choose a deadband and a zero deadband for the
monitored signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low
and low-low ranges of the measured value. The actual range of the measured value is
shown on the range output of MVGAPC function block. When a Measured value
expander block (RANGE_XP) is connected to the range output, the logical outputs of
the RANGE_XP are changed accordingly.
20.2.3.2
Receiving data
GUID-CAE4B020-7131-49BF-BA29-3EEE0EFEA2B8 v1
The GOOSE data must be received at function blocks. There are different GOOSE
receiving function blocks depending on the type of the received data. Refer to the
Engineering manual for more information about how to configure GOOSE.
Function block type
Data Type
GOOSEBINRCV
16 single point
GOOSEINTLKRCV
2 single points
16 double points
GOOSEDPRCV
Double point
GOOSEINTRCV
Integer
GOOSEMVRCV
Analog value
GOOSESPRCV
Single point
GOOSEXLNRCV
Switch status
Section 20
1MRK 502 071-UUS A
Station communication
746
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...