![background image](http://html.mh-extra.com/html/abb/relion-670-series-reg670/relion-670-series-reg670_applications-manual_4795754.webp)
20.3
LON communication protocol
IP14420-1 v1
20.3.1
Application
IP14863-1 v1
M14804-3 v5
Control Center
IED
IED
IED
Gateway
Star coupler
RER 111
Station HSI
MicroSCADA
IEC05000663-1-en.vsd
IEC05000663 V2 EN-US
Figure 325:
Example of LON communication structure for a substation automation
system
An optical network can be used within the substation automation system. This enables
communication with the IEDs through the LON bus from the operator’s workplace,
from the control center and also from other IEDs via bay-to-bay horizontal
communication. For LON communication an SLM card should be ordered for the
IEDs.
The fibre optic LON bus is implemented using either glass core or plastic core fibre
optic cables.
Table 74:
Specification of the fibre optic connectors
Glass fibre
Plastic fibre
Cable connector
ST-connector
snap-in connector
Cable diameter
62.5/125 m
1 mm
Max. cable length
1000 m
10 m
Table continues on next page
Section 20
1MRK 502 071-UUS A
Station communication
748
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...