The function is divided into two parts. The SOTF function will give operation from
step 2 or 3 during a set time after change in the position of the circuit breaker. The
SOTF function has a set time delay. The under time function, which has 2
nd
harmonic
restrain blocking, will give operation from step 4. The 2nd harmonic restrain will
prevent unwanted function in case of transformer inrush current. The under time
function has a set time delay.
Below the settings for switch on to fault logics are described.
SOTF
: This parameter can be set:
Disabled/SOTF/Under Time/SOTF+Under Time
.
SOTFSel
: This setting will select the signal to activate SOTF function;
CB position
open/CB position closed/CB close command
.
StepForSOTF
: If this parameter is set on step 3, the step 3 pickup signal will be used as
current set level. If set on step 2, the step 2 pickup signal will be used as current set
level.
HarmBlkSOTF
: This is used to
On
/
Off
harmonic restrain during SOTF conditions.
tSOTF
: Time delay for operation of the SOTF function. The setting range is 0.000 -
60.000 s in step of 0.001 s. The default setting is 0.100 s
t4U
: Time interval when the SOTF function is active after breaker closing. The setting
range is 0.000 - 60.000 s in step of 0.001 s. The default setting is 1.000 s.
ActUndrTimeSel
: Describes the mode to activate the sensitive undertime function. The
function can be activated by Circuit breaker position (change) or Circuit breaker
command.
tUnderTime
: Time delay for operation of the sensitive undertime function. The setting
range is 0.000 - 60.000 s in step of 0.001 s. The default setting is 0.300 s
9.4.3.5
Settings for each step (x = 1, 2, 3 and 4)
M15282-9 v12
Operation
: Sets the protection to
Enabled
or
Disabled
.
DirModeSelx
: The directional mode of step
x
. Possible settings are
Disabled
/
Non-
directional
/
Forward
/
Reverse
.
Characteristx
: Selection of time characteristic for step
x
. Definite time delay and
different types of inverse time characteristics are available.
Inverse time characteristic enables fast fault clearance of high current faults at the same
time as selectivity to other inverse time phase overcurrent protections can be assured.
This is mainly used in radial fed networks but can also be used in meshed networks. In
meshed networks, the settings must be based on network fault calculations.
1MRK 502 071-UUS A
Section 9
Current protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
369
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...