9.9.3
Setting guidelines
M13274-3 v8
The parameters for the Pole discordance protection CCPDSC (52PD) are set via the
local HMI or PCM600.
The following settings can be done for the pole discrepancy protection.
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
VBase
and
SBase
as applicable.
Operation
:
Disabled
or
Enabled
tTrip
: Time delay of the operation.
ContactSel
: Operation of the contact based pole discrepancy protection. Can be set:
Disabled
/
PD signal from CB
. If
PD signal from CB
is chosen the logic to detect pole
discrepancy is made in the vicinity to the breaker auxiliary contacts and only one signal
is connected to the pole discrepancy function. If the
Pole pos aux cont.
alternative is
chosen each open close signal is connected to the IED and the logic to detect pole
discrepancy is realized within the function itself.
CurrentSel
: Operation of the current based pole discrepancy protection. Can be set:
Disabled
/
CB oper monitor
/
Continuous monitor
. In the alternative
CB oper monitor
the
function is activated only directly in connection to breaker open or close command
(during 200 ms). In the alternative
Continuous monitor
function is continuously
activated.
CurrUnsymPU
: Unsymmetrical magnitude of lowest phase current compared to the
highest, set in % of the highest phase current. Natural difference between phase
currents in breaker-and-a-half installations must be considered. For circuit breakers in
breaker-and-a-half configured switch yards there might be natural unbalance currents
through the breaker. This is due to the existence of low impedance current paths in the
switch yard. This phenomenon must be considered in the setting of the parameter.
CurrRelPU
: Current magnitude for release of the function in % of
IBase
.
9.10
Directional underpower protection GUPPDUP (37)
SEMOD156693-1 v4
Section 9
1MRK 502 071-UUS A
Current protection
404
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...