Negative sequence inverse time characteristic
Negative sequence current
T
im
e d
el
ay
I2
tMax
tMin
IEC08000355-2-en.vsd
1
10
100
1000
10000
0.01
0.1
1
10
100
IEC08000355 V2 EN-US
Figure 202:
Inverse Time Delay characteristic, step 1
The example in figure
indicates that the protection function has a set minimum trip
time
t1Min
of 5 sec. The setting
t1Min
is freely settable and is used as a security
measure. This minimum setting assures appropriate coordination with for example line
protections. It is also possible to set the upper time limit,
t1Max
.
9.12.3.2
Pickup sensitivity
GUID-1D038486-7086-466F-A92F-30E1A47D0298 v3
The trip pickup levels Current
I2-1>
and
I2-2>
of NS2PTOC (46I2) are freely settable
over a range of 3 to 500 % of rated generator current
IBase
. The wide range of pickup
setting is required in order to be able to protect generators of different types and sizes.
After pickup, a certain hysteresis is used before resetting pickup levels. For both steps
the reset ratio is 0.97.
9.12.3.3
Alarm function
GUID-1B932D89-3233-4841-977A-5B61346B057B v2
The alarm function is operated by PICKUP signal and used to warn the operator for an
abnormal situation, for example, when generator continuous negative sequence current
capability is exceeded, thereby allowing corrective action to be taken before removing
1MRK 502 071-UUS A
Section 9
Current protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
423
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...