Table 49:
Available selection for voltage quantity within CVGAPC function
Set value for parameter
"VoltageInput"
Comment
1
PhaseA
CVGAPC function will measure the phase A voltage phasor
2
PhaseB
CVGAPC function will measure the phase B voltage phasor
3
PhaseC
CVGAPC function will measure the phase C voltage phasor
4
PosSeq
CVGAPC function will measure internally calculated positive
sequence voltage phasor
5
-NegSeq
CVGAPC function will measure internally calculated negative
sequence voltage phasor. This voltage phasor will be intentionally
rotated for 180° in order to enable easier settings for the directional
feature when used.
6
-3*ZeroSeq
CVGAPC function will measure internally calculated zero sequence
voltage phasor multiplied by factor 3. This voltage phasor will be
intentionally rotated for 180° in order to enable easier settings for
the directional feature when used.
7
MaxPh
CVGAPC function will measure voltage phasor of the phase with
maximum magnitude
8
MinPh
CVGAPC function will measure voltage phasor of the phase with
minimum magnitude
9
UnbalancePh
CVGAPC function will measure magnitude of unbalance voltage,
which is internally calculated as the algebraic magnitude difference
between the voltage phasor of the phase with maximum magnitude
and voltage phasor of the phase with minimum magnitude. Phase
angle will be set to 0° all the time
10
PhaseA-PhaseB
CVGAPC function will measure the voltage phasor internally
calculated as the vector difference between the phase A voltage
phasor and phase B voltage phasor (VA-VB)
11
PhaseB-PhaseC
CVGAPC function will measure the voltage phasor internally
calculated as the vector difference between the phase B voltage
phasor and phase C voltage phasor (VB-VC)
12
PhaseC-PhaseC
CVGAPC function will measure the voltage phasor internally
calculated as the vector difference between the phase C voltage
phasor and phase A voltage phasor (VC-VA)
13
MaxPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the
maximum magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the
minimum magnitude
15
UnbalancePh-Ph
CVGAPC function will measure magnitude of unbalance voltage,
which is internally calculated as the algebraic magnitude difference
between the ph-ph voltage phasor with maximum magnitude and
ph-ph voltage phasor with minimum magnitude. Phase angle will
be set to 0° all the time
It is important to notice that the voltage selection from table
regardless the actual external VT connections. The three-phase VT inputs can be
connected to IED as either three phase-to-groundvoltages VA, VB and VC or three
Section 12
1MRK 502 071-UUS A
Multipurpose protection
484
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for RELION 670 SERIES REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 44: ...38 ...
Page 66: ...60 ...
Page 102: ...96 ...
Page 200: ...194 ...
Page 442: ...436 ...
Page 486: ...480 ...
Page 508: ...502 ...
Page 514: ...508 ...
Page 524: ...518 ...
Page 658: ...652 ...
Page 736: ...730 ...
Page 774: ...768 ...
Page 828: ...822 ...
Page 829: ...823 ...