Test point
Reach
Set value
Comments
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
RLdFw x tan (ArgLd)
R
0
8
X
–0.2143 x RFPP/2
Exact: 0.8 x RFPP/2 (ArgDir=20°)
R
0.8 x RFPP/2
9
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
10
X
0.5 x X1
set
Exact –0.5 x R1
set
x
tan(ArgNegRes=30°)
R
–0.23 x X1
set
11
X
0.8 x X1
set
Exact –0.5 x R1
set
x
tan(ArgNegRes=30°)
R
–0.37 x X1
set
12
X
0.5 x X1
set
R
0.5 x R1
set
13
X
0
R
0.5 x RFPP
Table
is used in conjunction with figure
.
X1+XN
X
R (Ohm/loop)
50%
80%
1
2
3
4
5
6
7
8
9
10
11
80% of RLdFw
40% of RLdFw
RFPE
12
13
c
b =
Ar
gLD
alt. 80% of
RFPE (Load
encroachment)
120°
20°
a
IEC05000369-3-en.vsd
IEC05000369 V3 EN
Figure 27:
Distance protection characteristic with test points for phase-to-earth
measurements
Table
is used in conjunction with figure
.
Section 10
1MRK 506 355-UEN A
Testing functionality by secondary injection
114
Line distance protection REL670 2.1 IEC
Commissioning manual