8
Ground
9
TXD B
10
Control B
11
RXD B
13
Signal timing B
5,7,12,14,15
Not used
19.2.18.3
Functionality
The data format is HDLC. The speed for the transmission of the messages used is 64 kbit/
s.
A maximum of 100 meter of cable is allowed to ensure the quality of the data
(deviation from X.21 standard cable length).
Synchronization
The X.21 LDCM works like a DTE (Data Terminal Equipment) and is normally
expecting synchronization from the DCE (Data Circuit Equipment). The transmission
is normally synchronized to the Signal Element Timing signal when a device is a DTE.
When the signal is high it will read the data at the receiver and when the signal is low it
will write data to the transmitter. This behaviour can be inverted in the control register.
Normally an external multiplexer is used and it should act like the master.
When two X.21 LDCM is directly communicating with each other one must be set as a
master generating the synchronization for the other (the slave). The DTE Signal
Element Timing is created from the internal 64 kHz clock.
The Byte Timing signal is not used in ABB devices.
19.2.18.4
Technical data
Table 711:
Galvanic X.21 line data communication module (X.21-LDCM)
Quantity
Range or value
Connector, X.21
Micro D-sub, 15-pole male, 1.27 mm (0.050") pitch
Connector, ground selection
2 pole screw terminal
Standard
CCITT X21
Communication speed
64 kbit/s
Insulation
1 kV
Maximum cable length
100 m
Section 19
1MRK505222-UUS C
IED hardware
1128
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...