ANSI05000670-2-en.vsd
X1
R
X
0.5·
RFltFwdPP
Kr·X1
Kr·X1
X1
60 deg
60 deg
0.5·
RFltFwdPP
0.5·
RFltRevPP
0.5·
RFltRevPP
0.5·
RFltRevPP
1
Kr
tan(60 deg)
=
0.5·
RFltFwdPP
)
/
(
phase
W
)
/
(
phase
W
ANSI05000670 V2 EN
Figure 103:
The operation characteristics for FDPSPDIS (21) at phase-to-phase
fault (setting parameters in italic, directional lines drawn as "line-dot-dot-
line"), ohm/phase domain
In the same way as the condition for phase-to-ground fault, there are current conditions
that have to be fulfilled in order to release the phase-to-phase loop. Those are
according to equation
.
0
3
I
IMinPUPG
<
EQUATION2109-ANSI V1 EN
(Equation 30)
0
max
100
3
INBlockPP
Iph
I
<
×
EQUATION2110-ANSI V1 EN
(Equation 31)
where:
IMinPUPG is the minimum operation current for ground measuring loops,
3I0BLK_PP is 3I
0
limit for blocking phase-to-phase measuring loop and
Iphmax
is maximal magnitude of the phase currents.
Section 6
1MRK505222-UUS C
Impedance protection
224
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...