6.4.2
Principle of operation
6.4.2.1
Full scheme measurement
The execution of the different fault loops within the IED are of full scheme type, which
means that each fault loop for phase-to-ground faults and phase-to-phase faults are
executed in parallel.
The use of full scheme technique gives faster operation time compared to switched
schemes which mostly uses a phase selector element to select correct voltages and
current depending on fault type. So each distance protection zone performs like one
independent distance protection function with six measuring elements.
6.4.2.2
Impedance characteristic
The distance function consists of five instances. Each instance can be selected to be
either forward or reverse with positive sequence polarized mho characteristic
alternatively self polarized offset mho characteristics with reverse offset. The operating
characteristic is in accordance to figure
where zone 5 is selected offset mho.
Zs=0
R
jx
Mho, zone4
Mho, zone3
Mho, zone2
Mho, zone1
Offset mho, zone5
IEC09000143_2_en.vsd
X
R
Zs=Z1
Zs=2Z1
IEC09000143 V2 EN
Figure 117:
Mho, offset mho characteristic and the source impedance influence on the mho characteristic
1MRK505222-UUS C
Section 6
Impedance protection
241
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...