Signals ZOUT_n (outer boundary) and ZIN_n (inner boundary) in figure
related to the operation of the impedance measuring elements in each phase separately
(
n
represents the corresponding A, B and C). They are internal signals, calculated by
ZMRPSB (68) function.
The
tP1
timer in figure
serve as detection of initial power swings, which are
usually not as fast as the later swings are. The
tP2
timer become activated for the
detection of the consecutive swings, if the measured impedance exit the operate area
and returns within the time delay, set on the
tW
waiting timer. The upper part of
figure
(internal input signal ZOUT_A, ZIN_A, AND-gates and tP-timers) are
duplicated for phase B and C. All
tP1
and
tP2
timers in the figure have the same settings.
ANSI05000113-2-en.vsd
AND
ZINA
AND
DET-A
OR
AND
AND
ZOUTA
-loop
ZOUTB
ZOUTC
OR
detected
OR
-loop
0-tP1
0
0-tP2
0
0
0-tW
ANSI05000113 V2 EN
Figure 185:
Detection of power swing in phase A
ANSI01000057-2-en.vsd
DET-A
DET-B
DET-C
DET1of3 - int.
DET2of3 - int.
AND
AND
AND
OR
OR
ANSI01000057 V2 EN
Figure 186:
Detection of power swing for 1-of-3 and 2-of-3 operating mode
1MRK505222-UUS C
Section 6
Impedance protection
351
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...