6.12.2.2
Blocking logic
presents the logical circuits, which control the operation of the
underreaching zone (zone 1) at power swings, caused by the faults and their clearance
on the remote power lines.
PUZMUR
BLOCK
AND
PUZMOR
PUZMPSD
PUPSD
0-tDZ
0-tZL
AND
OR
AND
AND
AND
-loop
OR
PUZMURPS
BLKZMOR
AND
en06000237_ansi.vsd
0
0
ANSI06000237 V1 EN
Figure 190:
Control of underreaching distance protection (Zone 1) at power swings
caused by the faults and their clearance on adjacent lines and other
system elements
The logic is disabled by a logical one on functional input BLOCK. It can start only if
the following conditions are simultaneously fulfilled:
•
PUPSD functional input signal must be a logical zero. This means, that Power
swing detection (ZMRPSB, 68) function must not detect power swinging over the
protected power line.
•
PUZMPSD functional input must be a logical one. This means that the impedance
must be detected within the external boundary of ZMRPSB (68) function.
•
PUZMOR functional input must be a logical one. This means that the fault must
be detected by the overreaching distance protection zone, for example zone 2.
The PUZMURPS functional output, which can be used in complete terminal logic
instead of a normal distance protection zone 1, becomes active under the following
conditions:
Section 6
1MRK505222-UUS C
Impedance protection
358
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...