Name
Values (Range)
Unit
Step
Default
Description
tTRCrv3
0.005 - 100.000
-
0.001
13.500
Parameter TR for customer programmable
curve for step 3
tCRCrv3
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer programmable
curve for step 3
HarmRestrain3
Disabled
Enabled
-
-
Disabled
Enable block of step3 from harmonic restrain
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for step 4
tReset4
0.000 - 60.000
s
0.001
0.020
Reset time delay used in IEC Definite Time
curve step 4
tPCrv4
0.005 - 3.000
-
0.001
1.000
Parameter P for customer programmable
curve for step 4
tACrv4
0.005 - 200.000
-
0.001
13.500
Parameter A for customer programmable
curve for step 4
tBCrv4
0.00 - 20.00
-
0.01
0.00
Parameter B for customer programmable
curve for step 4
tCCrv4
0.1 - 10.0
-
0.1
1.0
Parameter C for customer programmable
curve for step 4
tPRCrv4
0.005 - 3.000
-
0.001
0.500
Parameter PR for customer programmable
curve for step 4
tTRCrv4
0.005 - 100.000
-
0.001
13.500
Parameter TR for customer programmable
curve for step 4
tCRCrv4
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer programmable
curve for step 4
HarmRestrain4
Disabled
Enabled
-
-
Disabled
Enable block of step 4 from harmonic restrain
Table 193:
OC4PTOC (51_67) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
MeasType
DFT
RMS
-
-
DFT
Selection between DFT and RMS
measurement
1MRK505222-UUS C
Section 7
Current protection
395
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...