Directional element will be internally enabled to operate as soon as Iop is bigger
than 40% of
IDirPU
and directional condition is fulfilled in set direction.
•
Relay characteristic angle
AngleRCA
, which defines the position of forward and
reverse areas in the operating characteristic.
Directional comparison step, built-in within directional supervision element, will set
EF4PTOC (51N/67N) function output binary signals:
1. PUFW=1 when operating quantity magnitude Iop x cos(φ -
AngleRCA
) is bigger
than setting parameter
IDirPU
and directional supervision element detects fault in
forward direction.
2. PUREV=1 when operating quantity magnitude Iop x cos(φ -
AngleRCA
) is bigger
than 60% of setting parameter
IDirPU
and directional supervision element detects
fault in reverse direction.
These signals shall be used for communication based ground-fault teleprotection
communication schemes (permissive or blocking).
Simplified logic diagram for directional supervision element with integrated directional
comparison step is shown in figure
1MRK505222-UUS C
Section 7
Current protection
407
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...