information) and OPENCMD (for opening command information). These inputs can be
connected to terminal binary inputs if the information are generated from the field (that
is from auxiliary contacts of the close and open push buttons) or may be software
connected to the outputs of other integrated functions (that is close command from a
control function or a general trip from integrated protections).
7.10.3
Function block
ANSI06000275-2-en.vsd
CCRPLD (52PD)
I3P*
BLOCK
BLKDBYAR
CLOSECMD
OPENCMD
EXTPDIND
52B_A
52A_A
52B_B
52A_B
52B_C
52A_C
TRIP
PICKUP
ANSI06000275 V2 EN
Figure 237:
CCRPLD (52PD) function block
7.10.4
Input and output signals
Table 229:
CCRPLD (52PD) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase currents
BLOCK
BOOLEAN
0
Block of function
BLKDBYAR
BOOLEAN
0
Block of function at CB single phase auto re-closing
cycle
CLOSECMD
BOOLEAN
0
Close command to CB
OPENCMD
BOOLEAN
0
Open command to CB
EXTPDIND
BOOLEAN
0
Pole discrepancy signal from CB logic
52b_A
BOOLEAN
1
Phase A Pole opened indication from CB
52a_A
BOOLEAN
0
Phase A Pole closed indication from CB
52b_B
BOOLEAN
1
Phase B Pole opened indication from CB
52a_B
BOOLEAN
0
Phase B Pole closed indication from CB
52b_C
BOOLEAN
1
Phase C Pole opened indication from CB
52a_C
BOOLEAN
0
Phase C Pole closed indication from CB
1MRK505222-UUS C
Section 7
Current protection
469
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...